Tranquility
®
30
(TT) Series
Models TTD/H/V 026 - 072
60 Hz - HFC-410A
INSTALLATION, OPERATION,
& MAINTENANCE
97B0075N05
Revised: 18 July, 2013
Table of Contents
Model Nomenclature 3
Unit Physical Data 6
Horizontal Installation 7
Field Conversion of Air Discharge 9
Horizontal Installation 10
Vertical Installation 11
Piping Installation 13
Water-Loop Heat Pump Applications 14
Ground-Loop Heat Pump Applications 15
Ground-Water Heat Pump Applications 17
Water Quality Standards 19
Electrical - Line Voltage 20
Electrical - Power Wiring 22
Electrical - Power & Low Voltage Wiring 23
Electrical - Low Voltage Wiring 24
Electrical - Thermostat Wiring 26
Blower Performance Data 27
ECM Blower Control 28
Typical Wiring Diagram - Units with CXM Board
and ECM Fan Motor (Single Phase) 30
Typical Wiring Diagram - Units with
ClimaDry
®
(Single Phase) 31
Typical Wiring Diagram - Units with CXM Board, 32
ECM Fan Motor, and MPC (DDC) CONTROLS
(SINGLE PHASE) 32
CXM Controls 33
DXM Controls 34
Safety Features - CXM and DXM Controls 36
ClimaDry
®
Modulating Reheat Option 38
Unit Starting and Operating Conditions 41
Piping System Cleaning and Flushing 42
Unit and System Checkout 44
Unit Start-Up Procedure 45
ClimaDry
®
II Option Corrections
(When Operating in Non-ClimaDry
®
Mode) 46
Unit Operating Conditions 47
Preventive Maintenance 49
Functional Troubleshooting 50
Performance Troubleshooting 51
Start-Up Log Sheet 52
Functional Troubleshooting 53
Warranty (U.S. & Canada) 54
Warranty (International) 55
Revision History 56

Questions and Answers

  • J
    Jon RodriguezAug 17, 2025
    How to troubleshoot main power problems in ClimateMaster Heat Pump?
    • K
      Kenneth EspinozaAug 17, 2025
      If your ClimateMaster Heat Pump has main power problems and the Green Status LED is off, check the line voltage circuit breaker and disconnect. Also, check for line voltage between L1 and L2 on the contactor, for 24VAC between R and C on CXM/DXM, and the primary/secondary voltage on the transformer.
  • A
    Anthony CantrellAug 22, 2025
    Why does my ClimateMaster Tranquility TTH049 Heat Pump unit short cycle?
    • R
      Robert PhillipsAug 22, 2025
      If your ClimateMaster Heat Pump unit short cycles, it could be due to several reasons. A dirty air filter can cause short cycling, so check and clean it. Also, the unit might be in 'test mode'; reset the power or wait 20 minutes for it to automatically exit this mode. The unit might be oversized for the space; check the sizing for the actual load of the space. Finally, the compressor might be overloaded, so check it and replace it if necessary.
  • G
    Gary AlvarezAug 25, 2025
    Why does only the fan run on my ClimateMaster Tranquility TTH049?
    • J
      Joseph PerryAug 26, 2025
      If your ClimateMaster Heat Pump only runs the fan, it could be due to the following reasons: * Thermostat position: Ensure the thermostat is set for heating or cooling operation. * Unit lockout: Check for lockout codes and reset the power. * Compressor Overload: Check the compressor overload and replace it if necessary. * Thermostat wiring: Check the thermostat wiring at the heat pump. Jumper Y and R for compressor operation in test mode.
  • S
    stacy85Aug 27, 2025
    What does LP/LOC Fault Code 3 mean on my ClimateMaster Tranquility TTH049 Heat Pump?
    • M
      Melanie DurhamAug 27, 2025
      If your ClimateMaster Heat Pump is showing the LP/LOC Fault Code 3, indicating low pressure or loss of charge, it could be due to insufficient charge. Check for refrigerant leaks. Alternatively, the compressor might be pumping down at start-up, so check the charge and start-up water flow.
  • J
    Justin FreemanAug 30, 2025
    Why does only the compressor run on my ClimateMaster Heat Pump?
    • B
      Brian YangAug 30, 2025
      If your ClimateMaster Heat Pump only runs the compressor, it could be due to the following issues: * Thermostat wiring: Check the G wiring at the heat pump. Jumper G and R for fan operation. * Fan motor relay: Jumper G and R for fan operation. Check for Line voltage across BR contacts. * Fan motor: Check for line voltage at the motor and check the capacitor. * Reversing valve: Set for cooling demand and check 24VAC on RV coil and at CXM/DXM board. If the RV is stuck, run high pressure up by reducing water flow and while operating engage and disengage RV coil voltage to push valve. * Thermostat setup: Check for ‘O’ RV setup not ‘B’. * Thermostat wiring: Check O wiring at heat pump. Jumper O and R for RV coil ‘click’.
  • L
    Laura CamachoSep 1, 2025
    What does LT1 Fault Code 4 mean on my ClimateMaster Tranquility TTH049 Heat Pump?
    • M
      michaelromeroSep 2, 2025
      If your ClimateMaster Heat Pump displays the LT1 Fault Code 4, which indicates a water coil low temperature limit, it could be due to: * Reduced or no water flow in heating: Check the pump operation or water valve operation/setting. Also, check water flow and adjust to proper flow rate. Clean or replace any plugged strainer or filter. * Inadequate antifreeze level: Check the antifreeze density with a hydrometer. * Improper temperature limit setting: Clip JW3 jumper for antifreeze (10°F [-12°C]) use. * Water temperature out of range: Bring the water temperature within design parameters. * Bad thermistor: Check the temperature and impedance correlation per chart.
  • K
    Karen DyerSep 4, 2025
    What does LT2 Fault Code 5 mean on my ClimateMaster Tranquility TTH049?
    • A
      Ashley FinleySep 4, 2025
      If your ClimateMaster Heat Pump displays the LT2 Fault Code 5, indicating an air coil low temperature limit, it may be caused by: * Reduced or no air flow in cooling: Check for a dirty air filter and clean or replace it. Also, check the fan motor operation and any air flow restrictions. Ensure that the external static isn't too high. * Air temperature out of range: Ensure that the entering air temperature is within design parameters. * Improper temperature limit setting: Normal airside applications will require 30°F [-1°C] only. * Bad thermistor: Check the temperature and impedance correlation per chart.
  • J
    josephjonesSep 6, 2025
    What causes Condensate Fault Code 6 on my ClimateMaster Tranquility TTH049 Heat Pump?
    • S
      Stacy GentrySep 6, 2025
      If your ClimateMaster Heat Pump displays Condensate Fault Code 6, it could be due to several reasons: * Blocked drain: Check for blockage and clean the drain. * Improper trap: Check trap dimensions and location ahead of vent. * Poor drainage: Check for piping slope away from the unit and the slope of the unit toward the outlet. Also, check the vent location. * Moisture on sensor: Check for moisture shorting to the air coil. * Plugged air filter: Replace the air filter. * Restricted Return Air Flow: Find and eliminate the restriction. Increase return duct and/or grille size.
  • A
    ariasstephanieSep 9, 2025
    What does Over/Under Voltage Code 7 mean on my ClimateMaster Tranquility TTH049 Heat Pump?
    • H
      Heather BlankenshipSep 9, 2025
      If your ClimateMaster Heat Pump displays the Over/Under Voltage Code 7, which auto-resets, it indicates a voltage issue. For Under Voltage, check the power supply and 24VAC voltage before and during operation, the power supply wire size, and compressor starting (consider a hard start kit). Also, check the 24VAC and unit transformer tap for correct power supply voltage. For Over Voltage, check the power supply voltage and 24VAC before and during operation, and the 24VAC and unit transformer tap for correct power supply voltage.
  • E
    Emily HallSep 12, 2025
    What does Unit Performance Sentinel Code 8 mean on ClimateMaster Tranquility TTH049?
    • K
      kathy31Sep 12, 2025
      If your ClimateMaster Heat Pump displays Unit Performance Sentinel Code 8, it indicates a performance issue. If in heating mode and LT2 is greater than 125°F [52°C], check for poor air flow or an overcharged unit. If in cooling mode and LT1 is greater than 125°F [52°C] or LT2 is less than 40ºF [4ºC], check for poor water flow or air flow.

Summary

Model Nomenclature

Configuration

Describes unit orientation (Vertical Up, Horizontal, Vertical Down).

Unit Size

Specifies the model's cooling/heating capacity range.

Controls

Details available control options (CXM, DXM, etc.).

General Information

Safety Precautions

General safety warnings, dangers, and cautions.

Pre-Installation and Preparation Steps

Tasks before unit installation begins.

Horizontal Installation

Mounting and Pitching Guidelines

How to hang and pitch units horizontally.

Vertical Installation

Unit Location Requirements

Criteria for selecting vertical install sites.

Piping Installation

Supply and Return Piping Guidelines

Best practices for connecting water loops.

Installer Cautions and Warnings

Critical safety and installation advice.

Ground-Loop Heat Pump Applications

Electrical - Line Voltage

Electrical Safety Precautions

Warnings and cautions for electrical work.

Electrical - Power Wiring

Power Wiring Safety Precautions

Disconnecting power and conductor types.

Electrical - Low Voltage Wiring

Thermostat Wiring and Connections

How to connect thermostats to the unit.

Electrical - Thermostat Wiring

Wiring Diagrams for Control Modes

Visual guides for thermostat connections.

CXM Controls

Control Overview and Test Mode Functionality

Basic operation and diagnostic tests.

Field Configuration Options (Jumpers;DIPs)

Setting control parameters via jumpers.

DXM Controls

Control Overview and Temperature Limit Settings

Basic operation and temp limit configuration.

Field Configuration Options (DIP Switches)

Setting control parameters via DIP switches.

Safety Features - CXM and DXM Controls

General Safety Features

Anti-short cycle, random start, fault retry, lockout.

Pressure and Temperature Protection Features

HP, LP, LT1, LT2, CO, Voltage protections.

Safety Features - CXM and DXM Controls

ClimaDry Modulating Reheat Option

Sequence of Operation for ClimaDry

How the ClimaDry system functions.

Piping System Cleaning and Flushing

Cleaning and Flushing Procedure

Steps to clean and flush the piping system.

Flushing;Purging Units with ClimaDry

ClimaDry Flushing Procedure

Steps for flushing ClimaDry coils.

Unit and System Checkout

Pre-Checkout Warnings and Cautions

POE oil, valve, and winterization safety.

Unit and System Checkout Procedures

Checklist for pre-power on checks.

Unit Start-Up Procedure

Startup Procedure Steps

Detailed sequence for unit startup.

Unit Start-Up Procedure

Test Mode and Safety Cautions

Using test mode and safety warnings.

Preventive Maintenance

Functional Troubleshooting

Troubleshooting Fault Codes

Diagnosing issues based on fault codes.

Operational Fault Diagnosis

Addressing common operational problems.

Performance Troubleshooting

Capacity and Pressure Issues

Diagnosing low capacity and pressure problems.

Functional Troubleshooting