Tranquility
®
30
(TT) Series
Models TTD/H/V 026 - 072
60 Hz - HFC-410A
INSTALLATION, OPERATION,
& MAINTENANCE
97B0075N05
Revised: 18 July, 2013
Table of Contents
Model Nomenclature 3
Unit Physical Data 6
Horizontal Installation 7
Field Conversion of Air Discharge 9
Horizontal Installation 10
Vertical Installation 11
Piping Installation 13
Water-Loop Heat Pump Applications 14
Ground-Loop Heat Pump Applications 15
Ground-Water Heat Pump Applications 17
Water Quality Standards 19
Electrical - Line Voltage 20
Electrical - Power Wiring 22
Electrical - Power & Low Voltage Wiring 23
Electrical - Low Voltage Wiring 24
Electrical - Thermostat Wiring 26
Blower Performance Data 27
ECM Blower Control 28
Typical Wiring Diagram - Units with CXM Board
and ECM Fan Motor (Single Phase) 30
Typical Wiring Diagram - Units with
ClimaDry
®
(Single Phase) 31
Typical Wiring Diagram - Units with CXM Board, 32
ECM Fan Motor, and MPC (DDC) CONTROLS
(SINGLE PHASE) 32
CXM Controls 33
DXM Controls 34
Safety Features - CXM and DXM Controls 36
ClimaDry
®
Modulating Reheat Option 38
Unit Starting and Operating Conditions 41
Piping System Cleaning and Flushing 42
Unit and System Checkout 44
Unit Start-Up Procedure 45
ClimaDry
®
II Option Corrections
(When Operating in Non-ClimaDry
®
Mode) 46
Unit Operating Conditions 47
Preventive Maintenance 49
Functional Troubleshooting 50
Performance Troubleshooting 51
Start-Up Log Sheet 52
Functional Troubleshooting 53
Warranty (U.S. & Canada) 54
Warranty (International) 55
Revision History 56

Questions and Answers

  • R
    Ricardo RomanAug 18, 2025
    How to troubleshoot main power problems in ClimateMaster Heat Pump?
    • J
      Jennifer BrownAug 18, 2025
      If your ClimateMaster Heat Pump has main power problems and the Green Status LED is off, check the line voltage circuit breaker and disconnect. Also, check for line voltage between L1 and L2 on the contactor, for 24VAC between R and C on CXM/DXM, and the primary/secondary voltage on the transformer.
  • R
    reginaperezAug 22, 2025
    Why does my ClimateMaster Tranquility TTV072 unit short cycle?
    • L
      lamamberAug 22, 2025
      If your ClimateMaster Heat Pump unit short cycles, it could be due to several reasons. A dirty air filter can cause short cycling, so check and clean it. Also, the unit might be in 'test mode'; reset the power or wait 20 minutes for it to automatically exit this mode. The unit might be oversized for the space; check the sizing for the actual load of the space. Finally, the compressor might be overloaded, so check it and replace it if necessary.
  • L
    Laura HesterAug 26, 2025
    Why does only the fan run on my ClimateMaster Heat Pump?
    • L
      Lucas KellyAug 26, 2025
      If your ClimateMaster Heat Pump only runs the fan, it could be due to the following reasons: * Thermostat position: Ensure the thermostat is set for heating or cooling operation. * Unit lockout: Check for lockout codes and reset the power. * Compressor Overload: Check the compressor overload and replace it if necessary. * Thermostat wiring: Check the thermostat wiring at the heat pump. Jumper Y and R for compressor operation in test mode.
  • A
    Anthony MorrisAug 28, 2025
    What does LP/LOC Fault Code 3 mean on my ClimateMaster Heat Pump?
    • R
      Robert TorresAug 28, 2025
      If your ClimateMaster Heat Pump is showing the LP/LOC Fault Code 3, indicating low pressure or loss of charge, it could be due to insufficient charge. Check for refrigerant leaks. Alternatively, the compressor might be pumping down at start-up, so check the charge and start-up water flow.
  • Q
    qhesterAug 30, 2025
    Why does only the compressor run on my ClimateMaster Tranquility TTV072 Heat Pump?
    • H
      Heather PeckAug 30, 2025
      If your ClimateMaster Heat Pump only runs the compressor, it could be due to the following issues: * Thermostat wiring: Check the G wiring at the heat pump. Jumper G and R for fan operation. * Fan motor relay: Jumper G and R for fan operation. Check for Line voltage across BR contacts. * Fan motor: Check for line voltage at the motor and check the capacitor. * Reversing valve: Set for cooling demand and check 24VAC on RV coil and at CXM/DXM board. If the RV is stuck, run high pressure up by reducing water flow and while operating engage and disengage RV coil voltage to push valve. * Thermostat setup: Check for ‘O’ RV setup not ‘B’. * Thermostat wiring: Check O wiring at heat pump. Jumper O and R for RV coil ‘click’.
  • D
    davismarcusSep 2, 2025
    What does LT1 Fault Code 4 mean on my ClimateMaster Tranquility TTV072?
    • T
      Theodore PerkinsSep 2, 2025
      If your ClimateMaster Heat Pump displays the LT1 Fault Code 4, which indicates a water coil low temperature limit, it could be due to: * Reduced or no water flow in heating: Check the pump operation or water valve operation/setting. Also, check water flow and adjust to proper flow rate. Clean or replace any plugged strainer or filter. * Inadequate antifreeze level: Check the antifreeze density with a hydrometer. * Improper temperature limit setting: Clip JW3 jumper for antifreeze (10°F [-12°C]) use. * Water temperature out of range: Bring the water temperature within design parameters. * Bad thermistor: Check the temperature and impedance correlation per chart.
  • D
    Debra McdanielSep 4, 2025
    What does LT2 Fault Code 5 mean on my ClimateMaster Heat Pump?
    • K
      Kathryn TuckerSep 4, 2025
      If your ClimateMaster Heat Pump displays the LT2 Fault Code 5, indicating an air coil low temperature limit, it may be caused by: * Reduced or no air flow in cooling: Check for a dirty air filter and clean or replace it. Also, check the fan motor operation and any air flow restrictions. Ensure that the external static isn't too high. * Air temperature out of range: Ensure that the entering air temperature is within design parameters. * Improper temperature limit setting: Normal airside applications will require 30°F [-1°C] only. * Bad thermistor: Check the temperature and impedance correlation per chart.
  • J
    jamie55Sep 7, 2025
    What causes Condensate Fault Code 6 on my ClimateMaster Heat Pump?
    • A
      amandamendozaSep 7, 2025
      If your ClimateMaster Heat Pump displays Condensate Fault Code 6, it could be due to several reasons: * Blocked drain: Check for blockage and clean the drain. * Improper trap: Check trap dimensions and location ahead of vent. * Poor drainage: Check for piping slope away from the unit and the slope of the unit toward the outlet. Also, check the vent location. * Moisture on sensor: Check for moisture shorting to the air coil. * Plugged air filter: Replace the air filter. * Restricted Return Air Flow: Find and eliminate the restriction. Increase return duct and/or grille size.
  • H
    Holly WongSep 9, 2025
    What does Over/Under Voltage Code 7 mean on my ClimateMaster Tranquility TTV072 Heat Pump?
    • H
      houstonnatalieSep 9, 2025
      If your ClimateMaster Heat Pump displays the Over/Under Voltage Code 7, which auto-resets, it indicates a voltage issue. For Under Voltage, check the power supply and 24VAC voltage before and during operation, the power supply wire size, and compressor starting (consider a hard start kit). Also, check the 24VAC and unit transformer tap for correct power supply voltage. For Over Voltage, check the power supply voltage and 24VAC before and during operation, and the 24VAC and unit transformer tap for correct power supply voltage.
  • K
    Kyle CampbellSep 12, 2025
    What does Unit Performance Sentinel Code 8 mean on ClimateMaster Heat Pump?
    • T
      taylor56Sep 12, 2025
      If your ClimateMaster Heat Pump displays Unit Performance Sentinel Code 8, it indicates a performance issue. If in heating mode and LT2 is greater than 125°F [52°C], check for poor air flow or an overcharged unit. If in cooling mode and LT1 is greater than 125°F [52°C] or LT2 is less than 40ºF [4ºC], check for poor water flow or air flow.

Summary

General Information and Safety

Critical Safety Warnings

Highlights DANGER, WARNING, CAUTION, and NOTICE statements for safe operation.

Horizontal Unit Installation

Vertical Unit Installation

Piping Installation

Water-Loop Heat Pump Applications

Ground-Loop Heat Pump Applications

Ground-Water Heat Pump Applications

Water Quality Standards

Provides standards for water quality to prevent scaling and corrosion.

Electrical - Line Voltage

Electrical - Power Wiring

Power Connection Guidelines

Explains connecting line voltage wires to the contactor and consulting data tables.

Electrical - Power & Low Voltage Wiring

Electrical - Low Voltage Wiring

Electrical - Thermostat Wiring

ECM Blower Control

Wiring Diagram: CXM & ECM Motor (Single Phase)

Wiring Diagram: ClimaDry (Single Phase)

Wiring Diagram: CXM, ECM, MPC (DDC)

CXM Control Operation

Field Configuration Options

Details jumper and DIP switch configurations for CXM control options.

DXM Controls

DXM Field Configuration Options

Details jumper and DIP switch configurations for DXM control options.

Safety Features - CXM and DXM Controls

Compressor Protection Features

Explains anti-short cycle, random start, and lockout protection.

Pressure and Temperature Limit Protection

Details high/low pressure, LT1/LT2 limits, and condensate overflow protection.

ClimaDry Modulating Reheat Option

ClimaDry Sequence Of Operation

Details the operating modes and thermostat compatibility for ClimaDry®.

UNIT STARTING AND OPERATING CONDITIONS

Operating Limits

Lists operating limits for air and water temperatures for optimal performance.

Unit Starting and Operating Conditions

Commissioning Conditions

Outlines commissioning limits for initial start-up and building conditioning.

Piping System Cleaning and Flushing

Piping System Cleaning and Flushing Procedure

Details the critical steps for cleaning and flushing the WLHP piping system.

Flushing;Purging Units with ClimaDry

ClimaDry Coil Flushing Procedure

Explains the process for flushing and purging the ClimaDry® hydronic circuit.

Unit and System Checkout

Unit Checkout Checklist

Lists essential checks for the unit before powering up the system.

System Checkout Checklist

Lists crucial checks for the overall system before powering up.

Unit Start-up Procedure

Cooling Mode Start-up

Guides through the start-up process for the cooling mode, including checks.

Heating Mode Start-up

Guides through the start-up process for the heating mode, including checks.

Unit Start-Up Procedure Details

Preventive Maintenance

Water Coil Maintenance

Guides on maintaining water coils based on water quality and loop type.

Filters Maintenance

Advises on inspecting, cleaning, and replacing air filters for optimal performance.

Condensate Drain Maintenance

Details cleaning and chemical treatment for condensate drains to prevent issues.

Compressor and Fan Motor Checks

Covers annual checks for compressor and fan motor amperage and condition.

Air Coil Cleaning

Guides on cleaning air coils and using surfactants for initial setup.

Functional Troubleshooting

Main Power and HP Fault Troubleshooting

Provides solutions for main power issues and HP fault code 2.

Low Pressure and High Pressure Troubleshooting

Guides on troubleshooting low/high pressure faults and lockout codes.

Temperature Limit and Condensate Faults

Covers troubleshooting LT1/LT2 faults and condensate drain issues.

Unit Operation Troubleshooting

Addresses issues like short cycling, fan-only operation, and unit not operating.

Performance Troubleshooting

Insufficient Capacity Troubleshooting

Helps diagnose and resolve issues causing insufficient cooling or heating capacity.

High Head Pressure Troubleshooting

Provides solutions for problems causing high head pressure in the system.

Low Suction Pressure Troubleshooting

Guides on identifying and fixing causes of low suction pressure.

Low Discharge Air Temperature in Heating

Helps troubleshoot low discharge air temperature issues during heating.

Functional Troubleshooting Analysis

Warranty (U.S. & Canada)

Limited Express Warranty Terms

Outlines the terms and conditions of the limited express warranty for North America.

Warranty Limitations and Exclusions

Specifies exclusions and limitations of the warranty coverage.

Warranty (International)

International Limited Express Warranty

Details the limited express warranty for products sold outside North America.

International Warranty Limitations

Lists exclusions and limitations applicable to international warranty claims.

ClimateMaster Tranquility TTV072 Series Specifications

General IconGeneral
CategoryHeat Pump
Cooling Capacity72, 000 BTU/h
RefrigerantR-410A
Compressor TypeScroll
ModelTTV072
Voltage208/230V