HRAT E - HRAT/HRAN
25English 09/02
OPERATING LIMITS
Meters
151015 20
Model
cPf
cQ
cdp
0
1
1
1
12%
0,985
1,02
1,07
20%
0,98
1,04
1,11
28%
0,974
1,075
1,18
35%
0,97
1,11
1,22
40%
0,965
1,14
1,24
Water thermal head min-max 3÷8
Hydraulic circuit pressure min-max (bars) 1÷3
Max. storage temperature (°C) 63
ETHYLENE GLYCOL SOLUTIONS
Water and ethylene glycol solutions used as a thermal
vector in the place of water reduce the performance
of the unit. Multiply the performance figures by the
values given in the following table.
0-5-10 -15 -20 -25
Freezing point (°C)
Percentage of ethylene glycol by weight
cPf: correction factor cooling capacity
cQ: correction factor flow rate
cdp: correction factor pressure drop
f1 correction factor capacity
fk1 correction factor compressor power input
fx1 correction factor total power input
FOULING FACTORS
The performance data given refer to conditions with
clean evaporator plates (fouling factor=1).
For different fouling factors, multiply the figures in the
performance tables by the coefficient given in the fol-
lowing table.
0011 50 41 35 32 29
0021 55 46 40 37 34
0025 55 46 40 37 34
0031 55 46 40 37 34
0041 58 49 43 40 37
0051 58 49 43 40 37
0061 58 49 43 40 37
0071 65 56 50 47 44
0091 65 56 50 47 44
0101 65 57 52 49 46
0121 65 57 52 49 46
0151 65 57 52 49 46
Octave band (Hz)
Gr. 63 125 250 500 1000 2000 4000 8000
Total dB(A)
Sound pressure level (dB)
0011 58 48 47 46 43 39 33 35 50
0021 65 55 54 53 50 46 40 42 55
0025 65 55 54 53 50 46 40 42 55
0031 63 53 52 51 48 44 38 40 55
0041 68 58 57 56 53 49 43 45 58
0051 68 58 57 56 53 49 43 45 58
0061 68 58 57 56 53 49 43 45 58
0071 75 65 64 63 60 56 50 52 65
0091 75 75 64 63 60 56 50 52 65
0101 75 75 64 63 60 56 50 52 65
0121 75 75 64 63 60 56 50 52 65
0151 75 75 64 63 60 56 50 52 65
AI
4,4 x 10
-5
0,86 x 10
-4
1,72 x10
-4
-
0,96
0,93
-
0,99
0,98
-
0,99
0,98
Fouling factors
(m
2
°C/W) f1
Evaporator
fk1 fx1
SOUND PRESSURE LEVEL
Reference point: at 1 m from the surface of the unit on the coil side and 1 m above the support surface.
5
10
15
20
25
30
8
28
35
40
45
43
-25 -15 -10 205-5 15 18 t°
t°
-10
-5
-3
-7
5
0
10
15
20
25
30 35 4540 50 t°
t°
To operate the
chiller, it is vital to
respect the condi-
tions given in the
table:
for model 0151 max
external air tempera-
ture = 40°C.
COOLING
ZONA
DI LAVORO
CONSIGLIATA
ZONA
DI LAVORO
CONSIGLIATA
HEATING
WATER OUTLET TEMPERATURE
WATER OUTLET TEMPERATURE
EXTERNAL AIR TEMPERATURE
EXTERNAL AIR TEMPERATURE