5 - AERAULIC CONNECTIONS
A. Thermically insulate the supply ducts to avoid heat
losses and condensate.
Avoid recirculation of exhaust/return air
A B
Size 2 310 276
Exhaust/return grille (GR200X )
Accessory separately supplied
Install on:
1. Fresh air intake
to be placed in an area with a low concentration of
impurities (dust, odours, exhaust fumes, etc.).
2. Ambient air exhaust
away from terraces, balconies, property boundary lines;
avoid windward zones.
2
1
Insulated flexible pipe
Rooftop exhaust/return
Unit installed in the attic with ejection/intake on the
roof. Install pipes and roof hoods (not provided by Cli-
vet).
A ≥ 500 mm
In areas with abundant snowfalls
Roof caps
Pipes
B. Avoid compressing the pipes and tight bends to
prevent any pressure drop.
The flexible pipe supplied by Clivet allows bends of
180° to be made without any compression and
without any reduction in pressure drop