8 - CONTROL
ATTENTION
The access to parameters or modifications are allowed only to the installer who assumes all responsibility, in case of
doubts please contact Clivet.
For any changes not permitted or not approved by Clivet, the same declines any responsibility for malfunctions and/or
damages to the unit/system.
PASSWORD-PROTECTED UNIT PARAMETERS (INSTALLER USE)
Number-
ing
Code DescripƟon default Minimum
maxi-
mum
unit
1.01 AUTOText0 Automatic temperature setting X- axis set point 0 15 0 50 °C
1.02 AUTOText1 Automatic temperature setting X- axis set point 1 24 0 50 °C
1.03 AUTOSet0 Automatic temperature setting Y- axis set point 0 19 0 50 °C
1.04 AUTOSet1 Automatic temperature setting Y- axis set point 1 25 0 50 °C
1.05 EnOnOff Unit switch mode
0: ON/OFF switch OFF signal is turned off, ON
boot
1: Wire controller control
2: Super terminal control
1 0 2 -
1.06 EnMode Mode setting mode
0: ON/OFF signal ,ON heating,OFF cooling
1 : Wire controller setting;
2 : Super terminal control
3 : Set to automatic mode
1 0 3 -
1.07 EnFHC Reserved 0 0 1 -
1.08 DeadZone Automatic mode setting mode switching backlash 2 1 10 °C
1.09 TimeECO Reserved 30 10 180 Min
1.1 0 TimeTestECO Reserved 3 1 1 0 Min
1.11 TypeFireMode Reserved 0 0 2 -
1.12 MaxReturn Reserved 6 -10 15 °C
1.1 3 MaxAnAux Reserved 100 50 100 %
1.1 4 Tregime Reserved 60 10 500 Min
1.15 TempAmAux-
En
Reserved 5 -10 15 °C
1.16 TimecomAux Reserved 20 10 120 Min
1.17 SetHeatECO Reserved 18 14 28 °C
1.18 Set Cool ECO Reserved 26 14 28 °C
1.19 BandPr Reserved 2 1 10 °C