8 - CONTROL
1.20 ReturnCool Reserved 0 -10 10 °C
1.21 ReturnHeat Reserved 0 -10 10 °C
1.22 OffsetT 1 Return air temperature correction 0 -10 10 °C
2.01 EnU R Cool Set whether there is dehumidification function in
cooling mode
0 0 1 -
2.02 DeltaU R Cool Dehumidification unit opening hysteresis 4 1 10 %
2.03 EnURHeat Reserved 0 0 1 -
2.04 DeltaU RHeat Reserved 4 1 10 %
2.05 EnProbeUrExt Outdoor humidity sensor 0 0 1 -
2.06 OffsetUrExt Outdoor humidity sensor correction 0 -50 50 %
2.07 EnProbeUrAmb Indoor humidity sensor 0 0 1 -
2.08 OffsetUrAmb Indoor humidity sensor correction 0 -50 50 %
3.01 Max frequence
in normal mode
Maximum frequency of compressor in normal
silent mode
60 56 72 HZ
3.02 Max SFLin
normal mode
The maximum gear position of the air blower in
the normal silent mode
3 2 4 -
3.03 Max EFLin
normal mode
The maximum gear position of the exhaust fan
in the normal silent mode
3 2 4 -
3.04 Max frequence
in super mode
Maximum frequency of compressor in ultra-
quiet mode
48 36 56 HZ
3.05 Max SFLin
super mode
Maximum fan position of air blower in ultra-quiet
mode
2 1 3 -
3.0 6 Max EFLin
super mode
Maximum position of exhaust fan in ultra-quiet
mode
2 1 3 -