43
OPERATION PARAMETER
This menu OPERATION PARAMETER is for installer or service engineer
reviewing the operation parameter.
The values shown on the screens are only indicative
Press MENU and select ASSISTANCE SETTING
Insert PASSWORD
Press OK
There are 3 pages for the operating parameters as following.
Press UP - DOWN to scroll
Press Adjust for modification
DEHUMIDIFICATION SETTING
Press MENU and select ASSISTANCE SETTING
Insert PASSWORD
Press OK
Select Humidity parameter
Enable parameter: 2.01 EnProbeUrSup =1
Set parameter: 2.03 DehumComModeSet (value 0,1,2)
0 = standard (10g/kg)
1 = Low humidity (8g/kg)
2 = eco (12g/kg)
DEHUMIDIFICATION (FROM MODBUS)
Enable from parameter keyboard: 2.01 EnProbeUrSup =1
Modbus:
Set parameter: 222 DehumComModeSet (value 0,1,2)
0 = standard (10g/kg)
1 = Low humidity (8g/kg)
2 = eco (12g/kg)