32 MSE-SC 65D-180F M43X41C6-03
Please contact the maker for informations.
9.6 System discharge
1. evacuate the system
2. evacuate the exchanger, use all the cocks presents
3. use compressed air to blow the exchanger
4. dry completely the exchanger by an hot air jet; for greater safety ll the exchanger with glycoled solution
5. protect the exchanger from the air
6. remove the drain plugs to the pumps
Any anti-freeze liquid contained in the system should not be discharged freely as it is a pollutant.
It must be collected and reused.
Before starting a washing the plant.
Example
A. emptying pump
Its recommended that the re-start after the stopping period is performed by a qualied technician, especially after seasonal stops or seasonal
switching.
When restarting, refer to what is indicated in the start-up” section.
Schedule technical assistance in advance to avoid hitches and to guarantee that the system can be used when required.
9.7 Control check list
intervention frequency (months) 1612
1 presence corrosion X
2 water lter cleaning X
3 check the exchanger eciency X
4 circulating pumps X
5 check of the xing and the insulation of the power lead X
6 check of the earthing cable X
7 electric panel cleaning X
8 capacity contactor status X
9 termina closing, cable insulation integrity X
10 voltage and phase unbalancing (no load and on-load) X
11 absorptions of the single electrical loads X
12 test of the compressor crankcase heaters X
13 leak control* X
14 survey of the refrigerant circuit operating parameters X
15 protective device test: pressure switches, thermostats, ow switches etc.. X
16 control system test: setpoint, climatic compensations, capacity stepping, water / air ow-rate variations X
17 control device test: alarm signalling, thermometers, probes, pressure gauges etc.. X
* European regulation 303/2008
Refer to the local regulations; and ensure correct adherance. Companies and technicians that eect interventions of installation, maintenance/
repairs, leak control and recovery must be CERTIFIED as expected by the local regulations. The leak control must be eected with annual
renewal.
9.8 Water lter
Check that no impurities prevent the correct passage of water.