M43X41C6-03 MSE-SC 65D-180F 33
9.9 Water side exchanger
It is very important for the exchanger to be able to provide the maximum thermal exchange, therefore it is essential for the inner surfaces to
be clean of dirt and incrustations.
Periodically check the dierence between the temperature of the supply water and the condensation temperature: if the dierence is greater
than 8°C–10°C it is advisable to clean the exchanger.
The clearing must be eected:
with circulation opposite to the usual one
with a speed at least 1,5 times higher than the nominal one
with an appropriate product moderately acid (95% water + 5% phosphoric acid)
after the cleaning rinse with water to inhibit the action of any residual product
9.10 Circulating pumps
Check:
no leaks
bearing status (anomalies are highlighted by abnormal noise and vibration)
the terminal protection covers are closed and the cable holders are properly positioned
9.11 crankcase heather
Check:
closure
Operation
9.12 Copeland scroll compressor
Compressor may stop Pumping With Motor Running
Turn Off And Wait Until Cool
May need More Than 1 Hour To Reset
Advanced Scroll Temperature Protection