Start-up - initial settings and functions
L
NOTE
Parameters 5.1 and 5.2 are set to YES, 5.3 will be automatically changed to YES.
The two zones can be controlled in dierent ways:
Zone 1 and Zone 2
Both are controlled according to the supply water temperature (T1).
Parameters 5.1 WATER FLOW TEMP. must be set to YES and 5.2 ROOM TEMP. must be set to NO.
Zone 1 will have setpoint T1S and Zone 2 will have setpoint T1S2 and the HMI will display these pages:
T1S T1S2
01-01-2021 23:59
7
OFF
ON
OFF
ON
35 35
01-01-2021 23:59
7
OFF
ON
OFF
ON
35
HOME PAGE ZONE 1 HOME PAGE ZONE 2
Fig. 87
Zone 1
With control based on the supply water temperature (T1) and Zone 2 with control based on the room air tem-
perature (Ta): it will be necessary to set parameters 5.1 WATER FLOW TEMP. to YES and
5.2 Room temp. to yes.
Zone 1 will have setpoint T1S and Zone 2 will have setpoint T1S2 and the HMI will display these pages:
T1S T1S2
01-01-2021 23:59
7
OFF
ON
OFF
ON
35 35
01-01-2021 23:59
7
OFF
ON
OFF
ON
25.0
HOME PAGE ZONE 1 HOME PAGE ZONE 2
Fig. 88
L
NOTE
Zone 2 has automatically controlled supply water temperature according to the climate curve. In double
zone systems, Zone 1 cannot have room air temperature control.
L
NOTE
Both zones can be equipped with an electromechanical thermostat to manage the request.

Other manuals for CLIVET WiSAN-YME 1 S 10.1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CLIVET WiSAN-YME 1 S 10.1 and is the answer not in the manual?

CLIVET WiSAN-YME 1 S 10.1 Specifications

General IconGeneral
BrandCLIVET
ModelWiSAN-YME 1 S 10.1
CategoryHeat Pump
LanguageEnglish

Related product manuals