M02R40C8-00 29/07/08 page 29
CIRCULATION PUMP
The pump is always activated with the units ON.
The delivery capacity is variable to soften the thermal shock to the compressors when the plant temperature is close to the
threshold limits.
Delivery capacity depends on the intake temperature:
SUMMER: high water temperature reduces delivery
WINTER: low water temperature reduces delivery
CIRCULATION PUMP – CONDENSER (RUNNING WATER)
The pump is started BEFORE the compressor start and stopped AFTER the condenser stop.
SET POINT
SUMMER - WINTER
The thermoregulator manages two set points:
SUMMER set-point for cooling (parameter 32)
WINTER set-point for heating (parameter 33)
The control is performed on the OUTLET TEMPERATURE, comparing it with the actual set-point value (visible at status 1).
SET-POINT CALCULATION:
desired medium outlet water temperature = 7°C
Project temperature differential = 5°C (that is inlet water = 12°C)
¼ of the project temperature differential = 5 / 4 = 1.25°C
set-point to be set = 7 – 1.25 = 5.7°C
SECONDARY SET POINT – ECO
A secondary set point can be used with different levels to the “normal” set point.
It is normally set to give lower energy consumption with respect to the comfort setting:
The SECONDARY SUMMER set point is higher than the SUMMER setting.
The SECONDARY WINTER set point is lower than the WINTER setting.
It can be set according to individual requirements.
Secondary summer set-point parameter 29
Secondary winter set-point parameter 30
It can be activated from the keyboard, supervisor unit or the remote control. To change it using the remote control refer to the
ELECTRIC WIRING paragraph.
MAINTENANCE
This way, the plant can be kept within the operating limits even when the unit is OFF or on STANDBY, for example during the
weekend or the night-time.
Periodically the system activates the circulation pump, measures the water temperature and activates the compressor, if
required, to take the water temperature to the set-point level.
Summer maintenance set-point par 42
Winter maintenance set-point par 43
This function is activated by parameters 44 (activate summer maintenance level) and 45 = 1 (activate winter maintenance
level).
DUAL CONTROLS FOR TEMPERATURE – RADIANT PANELS
With the optional kit, a mixed plant can be controlled:
Fan coil (with the set-points seen above)
Radiant panels (with specific radiant set-points)
The radiant set point can be determined in different ways, for further details see the ELECTRICAL CONNECTIONS section.
FUNCTIONING WITH ETHYLENE GLYCOL
The units foreseen to function with glycoled water come out from the premise with standard parameters.
After having added glycol ethylene to water, the technician will properly set the plant.
Parameter to modify:
32 Summer set point
77 Antifreeze heater set
80 Antifreeze alarm
84 Antifreeze pre-alarm threshold