M02R40C8-00 29/07/08 page 32
1
A
L
ARM
ST
A
T
US
S
E
T
OFF
unit in OFF.
by keypad
by supervisor
2
AL
AR
M
STATUS
SET
switching: long ON -
OFF
pressure
3
A
L
ARM
ST
A
T
US
S
E
T
11.6
OUTLET temperature
visualization
A
L
ARM
S
TA
TUS
SET
STB
Unità in :
• MANTEINTENANCE or
• In TRANSITION mode ( for ex. from heating to cooling or to domestic hot
H2O)
ACCESSIBLE PARAMETERS FROM REMOTE OR SERVICE KEYBOARD
num. Par. Description Value UM
29
Summer secondary Set Point
10 °C
30
Winter secondary Set Point
35 °C
32
Summer Set Point
5.7 °C
33
Winter Set Point
41.2 °C
42
Summer Set Point Maintenance
20 °C
43
Winter Set Point Maintenance
30 °C
44
Enables Summer Maintenance
0 num
45
Enables Winter Maintenance
0 num
77
Antifreeze heater set point
4 °C
80
Antifreeze alarm
4 °C
84
Limit of deactivation before reaching the antifreeze steps
4.5 °C
117
Domestic hot water set point
35 °C
163
Configures remote inputs: 1 = H/C by keypad or supervisor
216 Keypad address on Clivet Bus net: 7 =local; 1=remote 0 num
PARAMETER MODIFICATION
1
AL
AR
M
ST
A
T
U
S
SET
Push SET button
2
A
L
ARM
S
T
A
T
U
S
S
ET
Select the
parameter
3
A
L
ARM
S
T
A
T
U
S
S
ET
Modify the value
4
AL
AR
M
S
TA
T
U
S
SET
Select another
parameter
5
A
L
ARM
S
T
A
T
U
S
S
ET
SET to esc