M01W45H6-06
WSAT-SC
75C-180F
- CONTROL -
36
ACCESSIBLE PARAMETERS
PARAMETER MENU STRUCTURE
PARAMETERS
Set
LIST
Thermoreg.
Antifreeze
LIST
Maintenance
LIST
Set - point
LIST
SCHEDULING
Enscheduling
LIST
Configure
LIST
CLOCK SETUP
Clock
LIST
Data
LIST
menu: PARAMETERS – THERMOREG. – SET POINT DEFAULT values
90 / CEN SecondSetC Secondary cooling Set Point 12
118 / CEN SetCool Cooling Set Point 6.5
272 / CEN SetRecovery NOT USED 35
menu: PARAMETERS – THERMOREG. – MAINTENANCE
114 / CEN SetMantCool Summer maintenance setpoint 15
menu: PARAMETERS - THERMOREG.– ANTIFREEZE
115 / CEN AllFreeze Antifreeze alarm set 4
121 / CEN PreAF Antifreeze pre-alarm set 4.5
261 / CEN SetResist Antifreeze heater set 4
menu: PARAMETERS – SET – UNIT - EVAPORATORS
37 / EVAP SetResist Antifreeze heater set 4
39 / EVAP ALLFreeze Antifreeze alarm set 4
41 / EVAP PreAF Antifreeze pre-alarm set 4.5
KEYPAD USE
To enter in the SETUP menu
?
ESC
I
HOME
button F3 SETUP
To select the submenu
?
ESC
I
HOME
buttons ▲▼ F2 – F3
To access
?
ESC
I
HOME
button F1 ENTER
To scrolling voices
?
ESC
I
HOME
buttons
▲▼ F2 - F3
To go back a level of the menu
?
ESC
I
HOME
button ESC
SET UP menu:
PARAMETERS
set point modification
SCHEDULING
enables/disables timing
bands
CLOCK SETUP
Set the clock
ID Tast-Cen
(ATC ONLY)
PASSWORD
(ATC ONLY)
To go back to the main menu
?
ESC
I
HOME
button HOME