E9 no flow (manual reset) Ddained system
Turn the power off to reset it.Active 120 seconds
from the start-up
1Eb antifreeze probe Taf1 fault
2Eb antifreeze probe Taf2 fault
EC Slave unit module reduction
1Ed compressor drain temperature probe A
2Ed compressor drain temperature probe B
1EE refrigerant temperature probe T6A
2EE refrigerant temperature probe T6B
EF return water temperature probe
EH autotest error
EP drain temperature probe
Detection begins 10 minutes after start-up. The
protection intervenes if the heating Pc is ≥ 3.5 MPa
for 2 minutes or cooling Tz≥ 56ºC and the drain
temperature Tpmax <15ºC. The entire unit stops.
Turn the power off to reset it.
EU condenser total temperature probe Tz
P0 high pressure / drain temperature
If the protection intervenes 10 times in 150 minutes,
turn the power off to reset it
1P0 Compressor module 1 protection Due to high pressure protection
2P0 Compressor module 2 protection Due to high pressure protection
P1 low pressure
At start-up the low pressure switch is bypassed for
3 minutes.If the protection intervenes 10 times in
150 minutes, turn the power off to reset it.
If there is a remote control, turn the power off to
reset it.
P2 total condenser output high temperature Tz
P4 compressor A in protection
Absorption is not controlled during the first 10
seconds after the compressor has started. If the
protection intervenes 10 times in 150 minutes, turn
the power off to reset it. If there is a remote
control, turn the power off to reset it.
P6 module error
P7 condenser high temperature
P8 Reserved