Questions and Answers

  • S
    Shannon SharpAug 16, 2025
    Why is my CLIVET WSAT-YES 18.2 showing phases sequence control error?
    • D
      David PerkinsAug 16, 2025
      The error occurs when the three phases are not present at the same time and offset by 120°. To clear the error, restore the power supply.
  • K
    Kenneth CarterAug 19, 2025
    What to do if my CLIVET Heat Pump condenser has high temperature?
    • T
      Taylor HarperAug 19, 2025
      If the protection intervenes 3 times in 60 minutes, turn the power off to reset it. Also, check the positioning of the Twi - Two probes, the operation of the circulation pump, and ensure the flow range is within the permitted limits.
  • N
    Natalie BennettAug 22, 2025
    What to do if my CLIVET WSAT-YES 18.2 Heat Pump has low pressure?
    • T
      thomasvirginiaAug 22, 2025
      At start-up, the low pressure switch is bypassed for 3 minutes. If the protection intervenes 10 times in 150 minutes, turn the power off to reset it. If there is a remote control, turn the power off to reset it as well.
  • M
    Mercedes CollinsAug 26, 2025
    What to do if my CLIVET Heat Pump shows high room temperature probe T4?
    • M
      Mallory EnglishAug 26, 2025
      If the protection intervenes 3 times in 60 minutes, turn the power off to reset it.
  • A
    allenkeithAug 28, 2025
    What to do if my CLIVET Heat Pump shows antifreeze protection evaporator low temperature in cooling?
    • C
      Chris LewisAug 28, 2025
      If the protection intervenes 3 times in 60 minutes, turn the power off to reset it. Also, check that probe Two is correctly positioned.
  • P
    Pamela BrownAug 31, 2025
    What to do if my CLIVET WSAT-YES 18.2 Heat Pump shows high pressure or drain temperature?
    • G
      Gina Dunn MDAug 31, 2025
      If the protection intervenes 10 times in 150 minutes, turn the power off to reset it.
  • W
    Warren TurnerSep 3, 2025
    What to do if my CLIVET WSAT-YES 18.2 Heat Pump shows a drain temperature probe error?
    • C
      Chelsea BenderSep 3, 2025
      Detection begins 10 minutes after start-up. The protection activates if the heating Pc is ? 3.5 MPa for 2 minutes, or if cooling Tz? 56ºC and the drain temperature Tpmax
  • K
    Kathy SmithSep 6, 2025
    What to do if my CLIVET WSAT-YES 18.2 Heat Pump evaporator has low pressure in cooling?
    • M
      Mary JonesSep 6, 2025
      Check the water flow rate.
  • K
    Kimberly WilkinsSep 9, 2025
    What to do if my CLIVET Heat Pump displays a “Total” outlet water temperature probe Tw fault?
    • C
      Christina PowellSep 9, 2025
      When the number of units in line is 2 or more, check if the Tw sensor is faulty or is not required. When the number of units in line is 1, Tw = Two by default; check if the Tw sensor is faulty or is not required.
  • S
    Sharon LoveSep 12, 2025
    What to do if my CLIVET Heat Pump flow switch indicates no flow or sensor failure, or the pressure switch indicates system low pressure or sensor failure?
    • R
      Rhonda SmithSep 12, 2025
      To reset the system, it is necessary to remove power.