TW Probe - Total water
It must be installed on the supply of the unit, as far away as
possible.
SINGLE UNIT: antifreeze function
MODULAR UNIT: thermoregulation (see diagram below)
Water connections
Standard: Victaulic type
Option: to weld
Operations sequence
Before starting the unit pump:
1 Close all vents in the high points of the unit’s water circuit.
2 Close all drain shut-off valves in the low points of the unit’s
water circuit
Exchangers
Pumps
collectors
storage tanks
3 Thoroughly wash the system with clean water:
use the bypass to exclude the exchanger from the flow
(diagram on previous page) fill and drain the system several
times.
4 Apply additives to prevent corrosion, fouling, formation of
mud and algae.
5 Fill the system
do not use the unit pump
6 Conduct a leak test.
7 Isolate the pipes to avoid heat dispersions and formation of
condensate.
8 Leave various service points free (wells, vents, etc).
Neglecting to wash will lead to the filter having to be cleaned
many times and at worst may damage the exchangers and
compressors.