General technical data
Performance
SIZE 16.2 20.2 24.2 30.2 35.2 40.2
RADIANT PANELS
Cooling
Cooling capacity kW 1/4 64,0 72,0 80,0 92,0 101 113
EER 2 4,02 3,76 3,07 4,16 3,78 3,37
Water flow-rate l/s 1 3,14 3,54 3,93 4,50 4,89 5,56
User side exchanger pressure drops kPa 1 38 47 57 52 61 78
TERMINAL UNIT
Cooling
Cooling capacity kW 3 43 54 65 76 87 98
EER 2 3,30 3,14 2,76 3,25 3,07 2,79
SEER 5 4,97 4,81 4,65 5,37 5,15 4,95
ηs,c % 6 196 189 183 212 203 195
Water flow-rate l/s 5 2,14 2,51 3,06 3,60 4,21 4,58
User side exchanger pressure drops kPa 3 18 25 36 34 46 54
The Product is compliant with the ErP (Energy Related Products) European Directive. It includes the Commission delegated Regulation (EU) No 811/2013 (rated heat output ≤ 70 kW at
specified reference conditions) and the Commission delegated Regulation (EU) No 813/2013 (rated heat output ≤ 400 kW at specified reference conditions).
1. Entering/leaving water temperature user side 23/18 °C, Entering external exchanger air temperature 35 °C.
2. EER (EN 14511:2018) cooling performance coecient. Ratio between delivered coolimg capacitu and power input in compliance with EN 14511:2018.
3. User side entering/leaving water temperature 12/7 °C, external exchanger entering air 35 °C.
4. Data referred to unit operation with inverter frequency optimized for this application.
5. Data calculated according to the EN 14825:2016 Regulation.
6. The seasonal space cooling eciency ηs, c expressed in%.
Construction
SIZE 16.2 20.2 24.2 30.2 35.2 40.2
Compressor
Compressor type ROTARY INVERTER SCROLL INVERTER
Refrigerant R32
N° compressor Nr 2 2 2 2 2 2
Oil charge l 4,6 4,6 4,6 4,2 4,2 4,2
Refrigerant charge Kg 4,5 4,5 4,5 7,5 7,5 7,5
N° circuits Nr 1 1 1 1 1 1
User side exchanger
Type of internal exchanger 1 BHPE
Water content l 5,7 5,7 5,7 7,8 7,8 7,8
External Section Fans
Fans type BRUSHLESS DC MOTOR
N° fans Nr 2 2 2 3 3 3
Standard air-flow l/s 6944 6944 6944 10417 10417 10417
Installed unit power kW 0,8 0,8 0,8 0,9 0,9 0,9
Water circuit
Maximum water side pressure MPa 1 1 1 1 1 1
Minimum circuit water volume in
cooling
2 l 150 150 150 200 200 200
Total internal water volume l 6 6 6 6 6 6
Power supply
Standard power supply 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N
7. BPHE = plate exchanger
8. Entering/leaving water temperature user side 15/10 °C, external exchanger entering air 25°C (U.R. = 85%) - Minimum water volume that does not consider the volume of water
inside the unit.