9
ENGLISH
d) Pump down refrigerant system, if possible.
e) If avacuum is not possible, make amanifold so that refrigerant can be removed
from various parts of thesystem.
f) Make sure that cylinder is situated on thescales before recovery takes place.
g) Start therecovery machine and operate in accordance with manufacturer’s
instructions.
h) Do not overfill cylinders. (No more than 80 % volume liquid charge).
i) Do not exceed themaximum working pressure of thecylinder, even temporarily.
j) When thecylinders have been filled correctly and theprocess completed, make
sure that thecylinders and theequipment are removed from site promptly and all
isolation valves on theequipment are closed off.
k) Recovered refrigerant shall not be charged into another refrigeration system unless
it has been cleaned and checked.
18. Labelling
Equipment shall be labelled stating that it has been de-commissioned and emptied
of refrigerant. Thelabel shall be dated and signed. Ensure that there are labels on
theequipment stating theequipment contains flammable refrigerant.
19. Recovery
When removing refrigerant from asystem, either for servicing or decommissioning, it is
recommended good practice that all refrigerants are removed safely.
• When transferring refrigerant into cylinders, ensure that only appropriate refrigerant
recovery cylinders are employed. Ensure that thecorrect number of cylinders
for holding thetotal system charge are available. All cylinders to be used are
designated for therecovered refrigerant and labelled for that refrigerant (i.e. special
cylinders for therecovery of refrigerant). Cylinders shall be complete with pressure
relief valve and associated shut-off valves in good working order.
• Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs.
• Therecovery equipment shall be in good working order with aset of instructions
concerning theequipment that is at hand and shall be suitable for therecovery
of flammable refrigerants. In addition, aset of calibrated weighing scales shall be
available and in good working order.
• Hoses shall be complete with leak-free disconnect couplings and in good
condition. Before using therecovery machine, check that it is in satisfactory
working order, has been properly maintained and that any associated electrical
components are sealed to prevent ignition in theevent of arefrigerant release.
Consult manufacturer if in doubt.
• Therecovered refrigerant shall be returned to therefrigerant supplier in thecorrect
recovery cylinder, and therelevant Waste Transfer Note arranged. Do not mix
refrigerants in recovery units and especially not in cylinders.