This output is used at diesel engines equipped with fuel valve, which must be 
energized to stop the engine. 
The output is closed when the engine has to stop, remains closed while the 
engine is stopping and is opened back if the engine has successfuly stopped and 
stop time elapsed. For other stopping sequences please refer to Stop sequence 
chapter. 
The total time this output is continuously active is never shorter than Stop time, 
i.e. if the gen-set stops quickly, the output may remain closed eventhough all 
symptoms indicate the engine is stopped. 
This output is also closed if the engine begins to rotate unexpectedly, i.e. if it is 
started manually directly on the engine. To allow the engine to be operated 
manually without intervention from the controller, switch the controller to the 
emergency manual mode using the input Emerg. manual. 
NOTE:  
Learn more about this topic in the separate chapter Stop sequence.  
 
One second pulse is issued at this output when the engine is required to stop (i.e. 
this pulse does not commence stopping sequence but it is rather an actual 
command to engine physical stopping). The output is especially intended to be