Add or remove Force value
Change position of Force value functions (priority)
Change the name of the source setpoint
(available only for Force value 1-16 setpoints)
Select the value that should be forced (i.e. 
the value of the particular setpoint)
Rename binary input that 
triggers the forcing
ID of binary input
(1 for ForceValueIn 1 etc.)
Select source setpoint or value
 
For example if we add Force value:Force value 1 to be forced to ProcCtrlSingle:Export limit as value 0 
(DISABLED) by Binary Input FORCEVALUEIN 1 we can change the function of Export limit from ENABLED to 
DISABLED  by  activation  of  FORCEVALUEIN 1.  It  is  possible  to  rename  the  setpoint  to  e.g. 
Force value:ExportDisabled and Binary Input as well to e.g. DISABLEEXPLIM. The function will not change 
(only the corresponding names). 
It is possible to use several force value functions for one setpoint. If more than one forcing Binary Input is 
active, the one with the highest position (lowest number in the Force value dialog) is used. 
It is possible as well to use one Binary Input to force multiple setpoints (e.g. in case of complex function 
change). 
NOTE: 
It is possible only to force value or setpoint in other setpoint if their dimension and range are the same (e.g. 
only value with dimension in hours and which is Integer 16 to a setpoint with dimension hours and which is 
as well Integer 16). You may use PLC block Convert to change the dimension and range if needed.