IS-NT-Async-SPI, SW Version 1.2,   ©ComAp – February 2011                                
IS-NT-Async-SPI-1.2.PDF 
 
42
RPM 
Indication of RPM state. 
Sd Oil press B 
Engine Shut-down is activated by Binary input “Oil press”. 
ECU PwrRelay 
The output closes at the beginning of prestart and opens if the engine shall be stopped. 
This output can be used to indicate when the ECU should be powered up i.e. only while the engine is  
running.  
This output also influences evaluation of communication failure with ECU and related FLS alarms from 
analog inputs read from the ECU. If the output is configured (which means configured on physical binary 
output or VPIO output), the issuing of communication error is blocked during Prestart and Stopping 
procedure as shown in the picture. 
 
Fuel 
solenoid 
deactivation 
Beginning of 
Prestart 
ECU PwrRelay 
 
 
Hint:
 
The input must be configured on physical binary output or VPIO output. It is not enough to configure it as a 
PLC input for example. 
Generator Voltage and Frequency alarms indication 
Basic settings: FixVoltProtSel = PHASE-NEUTRAL 
Binary output name  Protection type  Based on setpoint 
BOC L1 under 
BOC L2 under 
BOC L3 under 
 
BreakerOpen & Cool-down 
 
Gener protect: Gen <V BOC, Gen V del 
BOC L1 over 
BOC L2 over 
BOC L3 over 
 
BreakerOpen & Cool-down 
 
Gener protect: Gen >V BOC, Gen V del 
Sd L1 over 
Sd L2 over 
Sd L3 over 
 
Shut-down 
Gener protect: Gen >V SD 
Gener protect: Gen V del 
Gen V L1-N 
Gen V L2-N 
Gen V L3-N 
BreakerOpen & Cool-down 
Shut-down 
Gener protect: Gen <V BOC 
Gener protect: Gen >V BOC 
Gener protect: Gen >V SD 
Gener protect: Gen V del 
 
 
 
 
ECU 
communication 
failure alarm 
blocked 
End of 
Prestart 
Engine 
stopped 
t