operation type (island, parallel or any transitions)  
Force value possibility: Yes 
Ld shed level   [ % ] (FV) 
When gen-set load exceeds this level for more than Ld shed delay time, controller proceeds to the next Load 
shedding stage - the next binary output Load shed x  is closed. 
Step:     1 % of Nomin power 
Range:    Ld recon level - 200 % of Nomin power 
Force value possibility: Yes 
Ld shed delay      [ s ]   (FV) 
Time delay for LD shed level limit. 
Step:     0,1 s 
Range:    0,0 – 600,0 s 
Force value possibility: Yes 
 
Ld recon level   [ % ] (FV) 
When gen-set load drops under this level for more than Ld recon delay time, controller proceeds to the lower 
Load shedding stage. The binary output for higher stage is opened (Load shed x). Automatic load 
reconnection works only when AutoLd recon = ENABLED. 
Step:     1 % of Nomin power 
Range:    0 - Ld shed level 
Force value possibility: Yes 
Ld recon delay      [ s ]   (FV) 
The amount of time that the load has to be under Ld recon level before the next part of the load is 
reconnected. 
Step:     1 s 
Range:    0 - 600 s 
Force value possibility: Yes 
 
AutoLd recon       [ DISABLED / ENABLED ]   (FV) 
Switch between manual and automatic reconnection of shedded load. 
DISABLED  Rising edge on binary input MAN load recon resets controller to the lower stage, but only if 
the load is under the Ld recon level. Ld recon delay is not important in this case. 
ENABLED   Load reconnection is automatic and depends on setpoints Ld recon level and Ld recon 
delay. Binary input MAN load recon has no function. 
Force value possibility: Yes 
Hint:
 
To understand Load shedding better see diagrams in section Load shedding (page 9 and 10). 
Timer settings  
Timer channel 1-16 
Defines the setting of particular timer channel. 
 
There is 16 channels, each defines occurrence date and time (year, month, day, hour, minute), duration time 
(in minutes, maximum is 24*60), repeating period (day, week, month, once). In case of week – day of the 
week selection, when should be executed + selection of repeating (every 1
st
, 2
nd
, 3
rd
 or 4
th
 week); In case of 
month – day of the month selection (e.g. every 3
rd
 day or every 2
nd
 Monday)   
 
Every channel can be disabled by blocking input. If blocking input is active then the timer is not activated 
even if it should be, according to it’s other settings.