Alarms and events
Events Warnings Shutdowns Shutdowns
Manual Start Warning Maintenance Emergency Stop Generator Undervoltage
Remote Start Low Battery Overspeed Generator Overfrequency
Manual Stop Low Fuel Level Underspeed Generator Underfrequency
Remote Stop External Warning 1 Low Oil Pressure Generator Overload
Auto On External Warning 2 High Coolant temperature Generator CCW Rotation
Auto Off External Warning 3 External Shutdown 1 Start Fail
Power On ECU Communication Error External Shutdown 2 Stop Fail
Island Operation External Shutdown 3 Battery Flat
Start on Low Battery GCB Fail Fuel Level SD
Stop After Charging Cycle Generator Overvoltage
ECU
For ECU configuration use PC software NanoEdit. For more details see InteliNano MRS 3 Reference Guide.
Technical data
Dimensions
Enclosure 118 mm x 108 mm x 40 mm
Cutout 96 mm x 96 mm
Power supply
Power supply range 8–36 VDC
Power supply drop-out immunity 100 ms
Power consumption 35 – 295 mA
Zero Power Mode consumption 52 - 344 µA
Binary outputs (up to 6)
Low current outputs (4) 500 mA
High current output (2) 6 A (long term) / 10 A (short term)
Total output current 10 A (long term) / 16 A (short term)
Binary inputs (up to 6)
Input resistance 1.5 kΩ
Closed contact voltage < 2 V
Open contact voltage > 3.5 V
Analog inputs (up to 3)
Galvanic insulation Not insulated
Electrical range 0–2500 kΩ
Resolution 0.1 Ω
Precision 2 % ± 5 Ω
Charging alternator preexcitation circuit
Excitation current 250 mA typical
Charging fail threshold 80 %
Operating temperature −20 to 70 °C
Operating humidity
95 % non-condensing
(IEC/EN 60068-2-30)
Protection degree (front panel)
IP65 with GASKET 4x405 only
IP50 without gasket
Storage temperature −30 to 80 °C
Generator measurements
Measurement input 3ph generator voltage
Measurement type True RMS
Voltage range 480 V Ph-Ph (277 V Ph-N)
Max. measured voltage 340 V Ph-N
Voltage accuracy 1 %
Current nominal/max. value 5 A / 10 A
Current accuracy 1 %
Frequency range 40–70 Hz
Frequency accuracy ±0.1 Hz
Magnetic pick-up
Voltage input range
4 Vpk-pk to 50 Vpk-pk (4 Hz–1 kHz)
6 Vpk-pk to 50 Vpk-pk (1–5 kHz)
10 Vpk-pk to 50 Vpk-pk (5–10 kHz)
Frequency input range 4 Hz–10 kHz
Frequency accuracy 0.1 %