Nortec SAM-e Installation | 20
Vertical Duct Installation for Nortec Mini SAM-e
1
2
Place header into duct. Use supplied
template to cut holes for steam and
condensate parts. Attach header to duct
using field-supplied fasteners.
Insert steam tubes with Insertion stop
washers, ensuring nozzles are
perpendicular to airflow. Using water to wet
the rubber grommets will facilitate
installation. Seal all ductwork.
3
Attach tube support bracket using supplied 1/4” lock-washer and 1/4” hex screws.
4
Attach bracket flanges to tube support
bracket using 5/16screws, washers, and
nylon lock-nut.
Bolt flanges to duct wall using field-supplied
1/2”-fasteners.
Condensate port at lowest point