37 | Nortec SAM-e Installation
Nortec SE Steam Line
Table 3: SE Steam-Line
Nortec
Unit
No. of
Steam
Outlets
Steam
output
[ lb ]
MED-L copper
tube nominal
steam line size
Stainless steel
tube diameter
(wall thickness
0.065”)
Steam loss
per foot in
condensation
[ lb/ft ]
Steam line
maximum
equivalent
length
SE 575 1 575 4” 4” 0.22 220 ft
SE 750 2 750 2 x 4” 2 x 4” 0.44 260 ft
SE 1050 2 1050 2 x 4” 2 x 4” 0.44 260 ft
• Based on 3” duct static pressure.
• Maximum duct static pressure for SE is 12” w.c.