Nortec SAM-e Installation | 38
Nortec RS Steam-Line
Table 4: SE Steam-Line
Nortec
Humidifier
Steam
output
[ lb ]
MED-L copper
tube nominal
steam line size
Stainless steel
tube diameter
(wall thickness
0.065”)
Steam loss per
foot in
condensation
[ lb/ft ]
Steam line
maximum
equivalent
length
RS 010
10
1-1/2
1-3/4”
0.11
12 ft
RS 015
15
1-1/2
1-3/4”
0.11
15 ft
RS 020
20
1-1/2
1-3/4”
0.11
18 ft
RS 030
30
1-1/2
1-3/4”
0.11
27 ft
RS 045
45
1-1/2
1-3/4”
0.11
43 ft
RS 065 65 1-1/2 1-3/4” 0.11 47 ft
RS 090 90 1-1/2 1-3/4” 0.11 48 ft
RS 135 135 2 x 1-1/2 2 x 1-3/4” 0.11 47 ft
RS 180
180
2 x 1-1/2
2 x 1-3/4”
0.11
48 ft
Based on 3” duct static pressure.
Maximum duct static pressure for resistive element units is 6”w.c.