³100mm 
(4in)
Optional braking resistors as required for the Drives
External: Mount on top surface of enclosure.
Internal: Mount in top part of enclosure. 
System controller 
Locate as required.
Signal cables
Plan for all signal 
cables to be routed at 
least 300mm (12in) 
distant from any 
power cable.
AC supply isolator, 
contactor, and 
fuses or MCBs  
Locate as required.
Enclosure
Drives
Ensure minimum 
clearances are 
respected.
Back-plate
³5mm 
(…in)
³100mm 
(4in)
Alternative 
location of 
fuses or 
MCBs
Locate as 
required.
³5mm 
(…in)
Power cables
Location 
of optional 
terminal 
block
Location of overload 
protection device
Optional braking resistors as required for the Drives
External: Mount on top surface of enclosure.
Internal: Mount in top part of enclosure. 
System controller
Locate as required.
Signal cables
Plan for all signal 
cables to be routed at 
least 300mm (12in) 
distant from any power 
cable.
RFI filters
Install a separate RFI 
filter for each Drive.
AC supply isolator, 
contactor, and 
fuses or MCBs  
Locate as required.
Power cables
Enclosure
Drives and 
RFI filters
Ensure minimum 
clearances are 
respected.
Back-plate
150mm 
(6in)
Alternative location of 
fuses or MCBs
Locate as required.
³5mm 
(…in)
Location 
of optional 
terminal 
block
Location of overload 
protection device
³100mm 
(4in)
³5mm 
(…in)
³5mm 
(…in)
Alternative location 
of fuses or MCBs
Locate as required.
➀ Consult Drive Centre for Filter details.
Panel Wiring Guidelines for Routine EMC Precautions
Panel Wiring Guidelines for Compliance with EMC Emission Standards
19