Unidrive M300/HS30 Quick Start Guide 25
Issue Number: 7
5.1 Saving parameters
When changing a parameter in Menu 0, the new value is saved when pressing the Enter button
to return to parameter view mode from parameter edit mode.
If parameters have been changed in the advanced menus, then the change will not be saved
automatically. A save function must be carried out.
Procedure
1. Select ‘Save' in Pr 00 or Pr mm.000 (alternatively enter a value of 1001 in Pr 00 or Pr mm.000)
2. Either:
Press the red reset button
Carry out a drive reset through serial communications by setting Pr 10.038 to 100
5.2 Restoring parameter defaults
Restoring parameter defaults by this method saves the default values in the drives memory. User
Security Status (Pr 10) and User Security Code (Pr 25) are not affected by this procedure.
Procedure
1. Ensure the drive is not enabled, i.e. drive is in inhibit or under voltage state.
2. Select 'Def.50’ or 'Def.60' in Pr 00 or Pr mm.000 (alternatively, enter 1233 (50 Hz settings) or
1244 (60 Hz settings) in Pr 00 or Pr mm.000).
3. Either:
Press the red reset button
Carry out a drive reset through serial communications by setting Pr 10.038 to 100

Other manuals for Control Techniques Unidrive M300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Control Techniques Unidrive M300 and is the answer not in the manual?

Control Techniques Unidrive M300 Specifications

General IconGeneral
BrandControl Techniques
ModelUnidrive M300
CategoryController
LanguageEnglish

Related product manuals