Type VXE reclosers are carefully tested and adjusted at
the factory to operate according to the published data.
Well-equipped test facilities, a detailed testing procedure,
and trained personnel assure accurate calibration.
Permanent records are kept of each reclosers test per-
formance. As a result, each recloser leaves the factory
ready for installation, and pre-installation testing is not
necessary. However, should verification of recloser oper-
ation be desired prior to installation, the following char-
acteristics can be checked:
1. Dielectric integrity of the recloser.
2. Minimum-trip current.
3. Operations sequence of the recloser.
4. Operation of the closing solenoid.
The test findings should agree with the settings pro-
grammed in the control. The recloser can be test-tripped
with a low-voltage ac source. However, to test operation
of the high-voltage closing solenoid, a high-voltage ac
source is required.
Safety Requirements
For personnel safety, the recloser, the electronic control,
and the high-voltage transformer must be enclosed in
suitable test cage to prevent accidental contact with haz-
ardous voltage and all grounding precautions must be
observed.
Test Equipment Required
The following equipment is required for these tests:
1. Variable autotransformer 120 V, 10 A.
2. 600:5 BCT Slip-on type bushing current trans-
former, set on the 600:5 tap.
3. Ammeter Must have a rating based on the level of
test current. Since the control is responsive to peak
current, it is recommended that metering responsive
to peak current be used when wave distortion is a
problem.
4. High-voltage transformer T
1 Used to operate high-
voltage closing solenoid (refer to Figure 13). Be sure
minimum allowable voltage, shown in Table 6, is
maintained at recloser terminals during the 45 cycle
interval the closing solenoid is energized.
5. High-voltage test set Must be capable of supplying
suitable voltages for determining the dielectric with-
stand capability of the recloser. Sensitive circuit
breakers should be included to prevent damage in
the event of a flashover. Refer to Service Information
S280-16-4, Type VXE Electronic Recloser Control
Tester Operation Instructions.
S280-16-1
15
!
SAFETY
FOR LIFE
TESTING
WARNING: Hazardous voltage. The switchgear
and high voltage transformer must be in a test
cage or similar protective device to prevent accidental
contact with the high voltage parts. Solidly ground all
equipment. Failure to comply can result in death,
severe personal injury, and equipment damage. T221.3
!
TABLE 6
Closing Solenoid Codes and Minimum Voltage
Closing Minimum Allowable
Closing Solenoid Voltage at Recloser
Solenoid Code When Solenoid is
Rating (kV) Number Energized (V)
VXE15
2.4 21 2040
4.164.8 22 3540
6.0 31 5100
7.27.62 23 6120
8.08.32 24 6800
VXE27
11.5 32 9775
12.013.2 30 10200
14.4 27 12240
Low-Voltage
Closing Coils
120 Vac/125 Vdc 26 95
240 Vac/250 Vdc 28 190