54
Kyle Form 4C Microprocessor-Based Recloser Control Programming Guide
Load Profile Monitor
Security Limits
Access Factory
Code Write Read Scroll High Low Incr Parameter Settings
180 0 0 NO 96 1 1 Load Profile - Reading Number --
• Data is accessible through the keyboard or Digital
Communications.
• From the keyboard, Access Codes 181 through 185
are accessible from Access Code 180 using the
SCROLL key.
• Data is read and recorded in 15-minute intervals and
stored in memory for the most recent 24 hours for a
total of 96 readings.
• Indicates the rms demand current for each phase
and ground.
• No security code is required for readout.
IMPORTANT: Load Profile Data will be lost
if power to the Form 4C control is lost. Load
Profile data will also be lost when the control
resets after a change to a TCC Group (Access
Code 70) or Line Frequency (Access Code 71).
Security Limits
Access Factory
Code Write Read Scroll High Low Incr Parameter Settings
181 -- 0 YES -- -- -- Time - Hour and Minute --
• Indicates the hour and minute of a specific phase
rms demand current profile.
Phase Current Phase Current Phase Current
Reading Hr:Min Ground Current Bushing 1-2 (A) Bushing 3-4 (A) Bushing 5-6 (A)
(180) (181) (182) (183) (184) (185)
1 15:30 2 258 261 262
2 15:15 0 260 257 259
3 15:00 2 253 251 255
4 14:45 1 261 255 257
5 14:30 1 257 248 257
TABLE 10
Load Profile Monitor Sample Data