54
Kyle Form 4C Microprocessor-Based Recloser Control Programming Guide
Load Profile Monitor
Security Limits
Access Factory
Code Write Read Scroll High Low Incr Parameter Settings
180 0 0 NO 96 1 1 Load Profile - Reading Number --
Data is accessible through the keyboard or Digital
Communications.
From the keyboard, Access Codes 181 through 185
are accessible from Access Code 180 using the
SCROLL key.
Data is read and recorded in 15-minute intervals and
stored in memory for the most recent 24 hours for a
total of 96 readings.
Indicates the rms demand current for each phase
and ground.
No security code is required for readout.
IMPORTANT: Load Profile Data will be lost
if power to the Form 4C control is lost. Load
Profile data will also be lost when the control
resets after a change to a TCC Group (Access
Code 70) or Line Frequency (Access Code 71).
Security Limits
Access Factory
Code Write Read Scroll High Low Incr Parameter Settings
181 -- 0 YES -- -- -- Time - Hour and Minute --
Indicates the hour and minute of a specific phase
rms demand current profile.
Phase Current Phase Current Phase Current
Reading Hr:Min Ground Current Bushing 1-2 (A) Bushing 3-4 (A) Bushing 5-6 (A)
(180) (181) (182) (183) (184) (185)
1 15:30 2 258 261 262
2 15:15 0 260 257 259
3 15:00 2 253 251 255
4 14:45 1 261 255 257
5 14:30 1 257 248 257
TABLE 10
Load Profile Monitor Sample Data