Changing Control Settings Using Access Codes
Use the following procedure to interrogate or change any control settings of parameters without dedicated keys. Refer
to Table 1 or to the control information label located inside the cabinet door to locate the desired parameter and appro-
priate access code. Enter the desired access code at Step 8.
Change Alternate Phase Minimum Trip Value
(Steps 2 through 6 are required to enter security code. If already in security, omit steps 2 through 6.)
Alternate phase minimum trip is changed from 120 A to 240 A.
Alternate ground minimum trip is changed from 60 A to 120 A.
10
Kyle Form 4C Microprocessor-Based Recloser Control Programming Guide