38
8-06
B.B. Time for Speed Search
d0.3 to d5.0 Sec
d0.5
8-07
Maximum Speed Search Current
Level
d30 to d200%
d150
8-08
Skip Frequency 1 Upper Bound
d0.0 to d400 Hz
d0.0
8-09
Skip Frequency 1 Lower Bound
d0.0 to d400 Hz
d0.0
8-10
Skip Frequency 2 Upper Bound
d0.0 to d400 Hz
d0.0
8-11
Skip Frequency 2 Lower bound
d0.0 to d400 Hz
d0.0
8-12
Skip Frequency 3 Upper bound
d0.0 to d400 Hz
d0.0
8-13
Skip Frequency 3 Lower Bound
d0.0 to d400 Hz
d0.0
8-14
Auto Restart After Fault
d0 to d10
d0
8-15
AVR Function
d0: AVR Function Enable
d1: AVR Function Disable
d2: AVR Function Disable when
Deceleration
d2
8-16
Dynamic Braking Voltage
d350 to d450V*
d380*
8-17
DC Braking Lower Bound Limit
d0.0 to d400 Hz
d0.0
Group 9: Communication Parameters
9-00
Communication Address @
d1 to d254
d1
9-01
Transmission Speed @
d0: Baud Rate 4800 bps
d1: Baud Rate 9600 bps
d2: Baud Rate 19200 bps
d3: Baud Rate 38400 bps
d1
9-02
Transmission Fault Treatment @
d0: Warn and Keep Operating
d1: Warn and Ramp to Stop
d2: Warn and Coast to Stop
d3: Keep Operating without Warning
d0
9-03
Modbus Communication
Watchdog Timer @
d0: Disable
d1 to d20: time setting (1 sec
increment)
d0
9-04
Communication Protocol @
d0: 7,N,2 (Modbus, ASCII)
d1: 7,E,1 (Modbus, ASCII)
d2: 7,O,1 (Modbus, ASCII)
d3: 8,N,2 (Modbus, ASCII)
d4: 8,E,1 (Modbus, ASCII)
d5: 8,O,1 (Modbus, ASCII)
d6: 8,N,2 (Modbus, RTU)
d7: 8,E,1 (Modbus, RTU)
d8: 8,O,1 (Modbus, RTU)
d0
d1