37
6-06
Electronic Thermal Overload
Relay Selection
d0 to d2
d2
6-07
Electronic Thermal Characteristic
d30 to d600 Sec
d60
6-08
Present Fault Record
d0: No Fault occurred
d1: Over Current (oc)
d2: Over Voltage (ov)
d3: Over Heat (oH)
d4: Over Load (oL)
d5: Over Load (oL1)
d6: External Fault (EF)
d7: Not Used
d8: Not Used
d9: Current exceed during Acceleration
(ocA)
d10: Current exceed during
Deceleration (ocd)
d11: Current exceed during Steady
State (ocn)
d12: Ground Fault (GF)
d0
6-09
Third Most Recent Fault Record
6-10
Group 7 Motor Parameters
7-00
Motor Rated Current @
d30 to d120%
d85
7-01
Motor No-Load Current @
d0 to d90%
d50
7-02
Torque Compensation @
d0 to d10
d01
7-03
Slip Compensation @
d0.0 to d10.0
d0.0
Group 8 Special Parameters
8-00
DC Braking Voltage Level
d0 to d30%
d0
8-01
DC Braking Time during Start-Up
d0.0 to d60.0 Sec
d0.0
8-02
DC Braking time during Stopping
d0.0 to d60.0 Sec
d0.0
8-03
Start-Point for DC Braking
d0.0 to d400 Hz
d0.0
8-03
Start-Point for DC Braking
d0.0 to d400 Hz
d0.0
8-04
Momentary Power Loss
Operation Selection
d0: Stop Operation after Momentary
Power Loss
d1: Continues after Momentary Power
Loss, speed search starts with Master
Frequency
d2: Continues after Momentary Power
Loss, speed search starts with
Minimum Output Frequency
d0
d1
8-05
Maximum Allowable Power Loss
Time
d0.3 to d5.0 Sec
d2.0