COTES C35 OPERATING AND SERVICE HANDBOOK page 20/71
Electric
heater,
max.
kW
4.6
4.6
5.7
6.9
8.0
4.6
6.9
2.3
3.4
External
duct
heater,
max.
kW
-
1.0
Maximum
fuse
(3x230V)
A
10
(32)
10
(32)
16
(32)
16
(32)
16
(32)
10
(32)
16
(32)
Minimum
fuse
(3x230V)
A
10
(20)
10
(20)
16
(25)
16
(25)
16
(32)
10
(20)
16
(32)
10
(32)
16
(32)
Nominal
power
consumptio
n
kW
4.92
5.10
6.25
7.42
8.50
4.86
7.26
3.9
5.3
Maximum
connected
load
kW
5.10
5.40
6.50
7.70
8.80
5.10
7.70
3.9
5.3
Voltage
(3x230V)
V
400
(3x230)
Frequency
Hz
50
Ground
(3x230V)
3PH+N+PE
(3PH+PE)
Sound
level with
duct (ISO
11201)
dB(A)
53
59
59
59
59
53
53
53
59
* Adjustable in Configuration-B and fully controlled in Configuration-C and Configuration-D.
Also adjustable in Configuration-A with Reg Air Fan Kit installed.
** Fully controlled in Configuration-C and Configuration-D.