SECTION 7 / CONDENSATION
OR HEAT RECOVERY UNIT
RECOMMENDED COMBINATIONS OF DEHUMIDIFIERS AND MODULES
Using an additional module alongside the dehumidifier unit might affect some of the nominal figures
provided in the data sheet. Key points are listed below.
The HR module is not fully compatible with all the dehumidifier units in the range, and it is important
to realize that the addition of a HR module will affect some of the nominal figures provided in the data
sheet. This applies particularly to the figures for available external pressure, which will no longer
apply because some pressure will be lost through the module itself. This loss of external pressure is
because the airflow must be increased and because the heat exchanger in the module itself adds a
resistance to the flow of air.
Note that the energy consumption of a Cotes dehumidifier in BASIC configuration will remain the
same with a HR module. However, the running time will fall due to the increased capacity when using
a HR module without modulating heat.
The LK module is not fully compatible with all the dehumidifier units in the range. The LK module will
impact the operating conditions for the dehumidifier.
The following guidelines with regard to compatibility must be respected: