COTES C35 OPERATING AND SERVICE HANDBOOK page 49/71
Check that the insulation on all electrical cables is intact, with no mechanical or heat damage.
Check that the insulation on the electric heater(s) is intact.
Check that all cables inside the electrical box are properly attached, all miniature circuit
breakers (MCBs) are switched on and all components are intact.
Test that all electric components are working as intended for example by following the
instructions in the “Commissioning” section of this handbook.
Service/repair work on this dehumidifier
Service area must be clear at all time.
Diagrams and manual must be kept near the machine.
Machine will automatically startup in case of power loss and recover of electricity.
Safety instructions
Before opening the dehumidifier, make sure that the electric current is switched off at the mains
before you open top cover or front door.
The QS10 safety switch should also be switched OFF and locked.
You should never just turn off the power to the dehumidifier while it is running. The correct procedure
is to press STOP C35 DEHUMIDIFIER (Configuration-A; press the operating button), after which the
machine runs a cooling cycle before the regeneration air fan stops. Turning off the dehumidifier
properly prevents any over-heating.
WARNING
Make sure that electric current is switched off at the mains
before you open top cover or front door
The QS10 safety switch should also be switched off and locked.