160
For L (live cable)
Turn the digital multimeter to 750V AC, use your one hand to hold the metal end, and then
the other hand insert the pen to the L port of the socket. See the following figure. If the
multimeter shows 120, then you can see current live cable connection is standard. If the
value is less than 60, then you can see current live cable connection is not proper or it is not
the live cable at all.
For N (Neutral cable)
Turn the digital multimeter to 750V AC, use your one hand to hold the metal end, and then
the other hand insert the pen to the N port of the socket. See the following figure. If the
multimeter shows 0, then you can see current N cable connection is standard. If the value is
more than 10, then you can see there is inductive current and the neutral cable connection is
not proper. If the value is 120, then you can know misconnected the neutral cable to the live
cable.