EasyManua.ls Logo

CPI CMP 200 - 2.8.5 Configuring Dual-Speed Starter 901297-15; 901298-15

CPI CMP 200
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CPI Canada Inc. Installation 2
2.8.5 Configuring dual-speed starter 901297-15 / 901298-15
Dual-speed starter part number 901297-15 / 901298-15 is a special configuration in which the low-speed
phase shift capacitors may be set to 15.5 uF or 28 uF. The 15.5 uF setting is intended for use in
installations where low-speed operation of CGR (GE) Statorix tubes is required. The high-speed
capacitance is automatically selected to either 3 uF or 6 uF according to the DIP switch setting.
Refer to figure 2-11. In configuration “A”, (28 uF) two leads are connected to the lower right capacitor.
Thus, the capacitor is in-circuit in this configuration. Configuration “B” (15.5 uF) has one of the leads
removed from the terminals of this capacitor, thus the capacitor is out of the circuit.
To change from configuration “A” to “B”, disconnect the interconnecting lower lead from the lower left
capacitor in figure 2-11, and connect it to the same terminal on the lower right. This removes the
lower right capacitor from the circuit.
To change from configuration “B” to “A” in figure 2-11, reconnect the lead between the two capacitors,
as shown. This connects the capacitor into the circuit.
After the phase shift capacitors are correctly configured, set the DIP switches as follows:
Locate the desired tube in table 2 of supplement 746026, which follows Chapter 2. With dual-speed
starter 901297-15 / 901298-15 set to configuration “A”, this starter is compatible with all tubes
requiring a 3 uF or 6 uF high-speed shift capacitor (unless indicated otherwise) and a 28, 30 or 31 uF
low-speed shift capacitor. When set to configuration “B”, it is only compatible with tubes requiring a 3
uF or 6 uF high-speed shift capacitor (unless indicated otherwise) and a 15.5 uF low-speed shift
capacitor.
Note the DIP switch setting for the desired tube as per table 2.
Set the DIP switches as per 2.8.2.
DUAL SPEED
STARTER
BOARD
CONFIGURATION “A”
CAPACITOR IN-CIRCUIT
(28 uF for TOSHIBA STATOR)
CONFIGURATION “B
CAPACITOR OUT-OF-CIRCUIT
(15.5 uF for LOW-SPEED CGR STATOR)
CMP200_FIG2-11A.CDR
DUAL SPEED
STARTER
BOARD
Figure 2-11: Selection of phase shift capacitance
Use and disclosure is subject to the restrictions on the title page of this CPI document.
CMP 200
X-Ray Generator Service Manual Ch # 901476-02 Rev. P Page 2-27

Related product manuals