Output freq.[Hz]
tt
t : Retry time H24
time
First Fault
Second Fault
First Retry
Second Retry
5.3.8 Auto Restart
H23:
Retry Number (Factory default: 0)
Range: 0 - 10 times
H24: Retry Time (Factory default: 0.5 sec.)
Range:0.0 - 10.0 sec.
H25: Retry Mode (Factory default: 0)
Range:0: Non-operation during LV fault and retry
1: Non-operation during LV fault
2: Non-operation during retry
3: Driving in all faults
These functions are used so the drive can reset itself automatically from all drive
faults except Low Voltage or BX fault. The operator can set the maximum number of
auto-restart trials through H23,Retry Number, and Retry Time (a waiting time before
the next restart attempt) through H24. The Auto-Restart works in conjunction with
the Speed Search Mode, see Section 5.3.11. See Fig. 5.3.8.
Fig. 5.3.8: Auto Restart Function