EasyManua.ls Logo

Crown Macro-Tech 2402 - Advanced Protection Systems Explained; ODEP Protection Technology; Standby Mode Operation and Triggers; Transformer Thermal Protection Circuitry

Crown Macro-Tech 2402
43 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Macro-Tech
®
602/1202/2402 Power Amplifiers
Page 14
Reference Manual
Fig. 3.6 Parallel-Mono Wiring
3.3.3 Parallel-Mono Operation
Parallel-Mono mode is intended for driving loads with a
net impedance of less than 4 ohms. (See Bridge-Mono
if the load is 4 ohms or greater.) Installing the amp in
Parallel-Mono mode is very different from the other
modes and requires special attention.
CAUTION: Do not attempt to operate in Stereo or
Bridge-Mono mode until the Parallel-Mono jumper
is first removed. Failure to do so will result in high
distortion and excessive heating.
To put the amplifier in Parallel-Mono mode, turn it off
and slide the stereo/mono switch to the left (as you face
the back panel). Connect the input signal to Channel 1
only. The Channel 2 input and level control are by-
passed in this mode, so they should not be used.
Note: It is normal for the IOC indicator of Channel 2 to
remain lit in Parallel-Mono mode.
Install a jumper wire between the red binding posts of
both Channel 1 and 2 that is at least 14 gauge in size.
Then, connect the load to the output of Channel 1 as
shown in Figure 3.6. The positive lead from the load
connects to the red binding post of Channel 1 and the
negative lead from the load connects to the black bind-
ing post of Channel 1.
CAUTION: Remove the jumper wire before chang-
ing to Stereo or Bridge-Mono mode.

Table of Contents

Other manuals for Crown Macro-Tech 2402

Related product manuals