EasyManuals Logo

CS Instruments DS 400 User Manual

CS Instruments DS 400
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
DS 400 Side 26 of 36
8.5 Alarm Settings
Modbus
Register
Modbus
Address
No.of
Byte
Data Type
Description
Default
Setting
Read
Write
Comment
4001
4000
2
word
Channel / Value
0
R
Alarmsettings #1 *6)
4002
4001
2
word
Relais
0
R
relais setting *7)
4003
4002
4
float
upper warning
value
0
R
4005
4004
4
float
Hysteresis for
above
0
R
4007
4006
4
float
upper alarm
value
0
R
4009
4008
4
float
Hysteresis for
above
0
R
4011
4010
4
float
lower warning
value
0
R
4013
4012
4
float
Hysteresis for
above
0
R
4015
4014
4
float
lower alarm
value
0
R
4017
4016
4
float
Hysteresis for
above
0
R
4019
4018
4
float
Reserved
4021
4020
2
word
Channel / Value
0
R
Alarmsettings #2 *6)
4022
4021
2
word
Relais
0
R
relais setting *7)
4023
4022
4
float
upper warning
value
0
R
4025
4024
4
float
Hysteresis for
above
0
R
4027
4026
4
float
upper alarm
value
0
R
4029
4028
4
float
Hysteresis for
above
0
R
4031
4030
4
float
lower warning
value
0
R
4033
4032
4
float
Hysteresis for
above
0
R
4035
4034
4
float
lower alarm
value
0
R
4037
4036
4
float
Hysteresis for
above
0
R
4039
4038
4
float
Reserved

Questions and Answers: