04. OPERATION
4.2 Start-up -Check that the boiler and radiator system are filled with water.
- Vent the boiler by opening by hand the safety valve on the top of the
boiler. Make a subsequent filling of the system when needed.
- Check that all tube connections are tight and that the connections for
chimney and combustion are correctly performed.
- Check that the oil pipes of the oil burner are correctly performed and
that there is oil in the tank.
- Adjust the thermostat within the recommended range
- Put the main switch of the switch panel to position 1.
- Put the burner switch to position 1.
- Check that the burner starts immediately. The burner is factory set.
- Put the switch for the circulation pump into position1.
- When the boiler and the radiator system have reached the working
temperature, make a new venting through the safety valve.