page 8
2.6.4.4 Advanced Settings / Set Hour Meter
Starting from the main menu, choose "Advanced Settings" then,
choose "Set Hour Meters". From the next menu listing choose
"Reset All".
Return to the main menu by utilizing the up / down arrows on panel
and select "Exit".
2.6.4.5 Exiting Menu Mode
This can be accomplished by selecting the "Exit" menu choice.
3.0 Operation
Buttons are utilized for menu navigation as described earlier.
3.1 Auto-range (BDI)
Curtis enGage™ IV has an operating voltage range for V+ from 12 to
80 VDC +/- 25%. The source to which pin J1-17 is connected will
configure the instrument for the correct Battery Discharge Indicator
system voltage. Refer to table below for J1-17 connection depending
on voltage range desired.
Pin J1-17 Connection Guide
When configured to display other instruments (not BDI), terminal J1-
17 is unused. Note that for all analog sender inputs (J1-3, J1-4, J1-5,
J1-6), the sender range is factory configured.
System Voltage J1-17Connection
12 No Connection
24 V+
36 V-
48 No Connection
60 V+
72 V-
80 No Connection