problem Possible Cause Solution
The circuit breaker
button is projecting
from the back of the
unit.
The circuit breaker has been tripped
due to an overload.
Turn the UPS off and unplug at least one piece of equipment. Wait 10 seconds,
reset the circuit breaker by pressing the button, and then turn the UPS on.
The UPS does not
perform the expected
runtime.
The battery is not fully charged. Recharge the battery by leaving the UPS plugged in.
The battery is worn out.
Contact CyberPower Systems about replacement batteries at:
cyberpowersystems.com/support.
The UPS will not turn
on.
The on/off switch is designed to
prevent damage from rapidly turning
it off and on.
Turn the UPS off. Wait 10 seconds and then turn the UPS on.
The unit is not connected to an AC
outlet.
The unit must be connected to a 120V 60Hz outlet.
The battery is worn out.
Contact CyberPower Systems about replacement batteries at:
cyberpowersystems.com/support.
Mechanical problem. Contact CyberPower Systems at: cyberpowersystems.com/support.
PowerPanel®
Personal is inactive
(all icons are gray).
The USB /serial cable is not
connected.
Connect the USB/serial cable to the UPS unit and an open USB /serial port on the
back of the computer. You must use the cable that came with the unit.
The USB / serial cable is connected
to the wrong port.
Check the back of the computer for an additional USB /serial port. Move the cable to
this port.
The unit is not providing battery
power.
Shut down your computer and turn the UPS off. Wait 10 seconds and turn the UPS
back on. This should reset the unit.
Additional troubleshooting information can be found at “Support” at www.CyberPowerSystems.com
TECHNICAL SPECIFICATIONS
Serin CP900AVR CP1200AVR CP1500AVRT
Model CP900AVR2 CP1200AVR2 CP1500AVRT2
Capacity 900VA / 560W 1.200VA / 720W 1.500VA / 900W
Nominal Input Voltage 120V
Input Frequency 60 Hz ± 3 Hz
On-Battery Output Voltage 120 Vac ± 5%
Max. Load for UPS Outlets (5 Outlets) 900VA / 560W 1.200VA / 720W 1.500VA / 900W
Max. Load for Full-Time Surge Protection outlets
(10 Outlets)
12 A 12 A 12.5 A
On-Battery Output Wave Form Simulated Sine Wave
Operating Temperature + 32°F to 104° F / 0° C to 40° C
Operating Relative Humidity 0 to 95% non-condensing
Size (W x H x D) 3.9″ x 9.8″ x 13.7″ (99 x 249 x 348 mm)
Net Weight 21.83 lbs / 9.9 kg 21.83 lbs / 9.9 kg 24A lbs / 10.91 kg
Battery Type CyberPower / RB127OX2C CyberPower / RB127OX2C CyberPower / RB1290X2
Typical Battery Recharge Time 8 hours to 90% capacity from total discharge
Typical Battery Life 3 to 6 years. depending on the number of discharge/recharge cycles
Recommended Battery Sealed Maintenance Free Lead Acid Battery
Safety Approvals UL1778 (UPS). CSA C22.2 No. 107. FCC/DoC Class B
SYSTEM FUNCTION BLOCK DIAGRAM
CYBERPOWER GREEN POWER UPS™ TECHNOLOGY
CYBERPOWER GREENPOWER UPS™ TECHNOLOGY
Advanced Energy-Saving Design
The GreenPower UPS™ has a high-efficiency charger, which makes it the most energy-efficient UPS in its class. The advanced high-frequency charging
system significantly improves charging efficiency and conserves energy. As a result of this advanced design, the GreenPower UPS™ uses less energy
compared to competitive models. The GreenPower UPS™ is manufactured in accordance with the Restriction on Hazardous Substances (RoHS) directive
making it one of the most environmentally-friendly UPS systems on the market today.