Automatic Voltage Regulators
increase low or decrease high voltage to a computer
safe 110/120 volts. The AVR automatically provides
battery back-up power if line voltage drops below 90
volts or exceeds 140 volts.
AVR
INCONSISTENT
UTILITY POWER
CONSISTENT
SAFE POWER
1 2 3 4
5 6
UNINTERRUPTIBLE
POWER SUPPLY
E187679
6G48
IN
AC INPUT
Push To
RESET
WIRING
FAULT
OUT
SERIAL
13 7 8 9 10 11 12
INSPECTION
The box should contain the following:
(1) PowerPanel
®
Business Edition software (CD); (1) RS232 cable (DB-9); (1) USB cable (A+B type); (1) Telephone communication cable;
(1) user manual; (1) Warranty registration card; (1) UPS unit.
OVERVIEW
The OR500LCDRM1U/OR700LCDRM1U provides automatic voltage regulation for inconsistent utility
power. The OR500LCDRM1U/OR700LCDRM1U features 1030 Joules of surge protection, and provides
battery backup during power outages. The OR500LCDRM1U/OR700LCDRM1U ensures consistent
power to your computer system and its included software will automatically save your open files and
shutdown your computer system during a utility power loss.
AUTOMATIC VOLTAGE REGULATOR
The OR500LCDRM1U/OR700LCDRM1U stabilizes inconsistent utility power. The incoming utility power
may be damaging to important data files, but with Automatic Voltage Regulation, the computer will not
experience damaging voltage levels. An Automatic Voltage Regulator automatically increases low or decreases high voltage to a consistent,
computer safe 110v/120v. The unit’s powerful sealed lead-acid batteries will provide power only if the incoming voltage drops below 90v or
increases above 140v.
HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT
1. Make sure that the total Volt-Amp (VA) requirements of your computer, monitor, and peripheral equipment does not exceed 500 VA/
700VA.
2. Ensure that the equipment plugged into the four battery power-supplied/surge outlets does not exceed the UPS unit¡¦s rated capacity
(500VA/300W for OR500, 700VA//400W for OR700). If the rated unit capacities are exceeded, an overload condition may occur and cause
the UPS unit to shut down and the circuit breaker to trip.
3. If the power requirements of your equipment are listed in units other than Volt-Amps (VA), convert Watts (W) or Amps (A) into VA by
performing the calculations below. Note: The equation listed below only calculates the maximum amount of VA that the equipment can use,
not what is typically used by the equipment at given time. Users should expect usage requirements to be approximately 60% of the
maximum power requirements:
Watts (W) x 1.82 = VA or Amps (A) x 120 = VA
Add the totals up for all pieces of equipment and multiply this total by 0.6 to calculate the approximate requirements.
There are many factors that can affect the amount of power that your computer system will require. The total load that you will be placing on
the battery-powered outlets should not exceed 80% of the unit's capacity.
Office Rack Mount UPS
OR500LCDRM1U/OR700LCDRM1U
User’s Manual
K01-0000030-01
This manual contains important instructions that should be followed during installation and mainte-nance of the UPS and batteries. Please
read and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to
unpack, install, or oper-ate.
CAUTION! The UPS must be connected to a grounded AC power outlet with fuse or circuit breaker protection. DO NOT plug the UPS into
an outlet that is not grounded. If you need to de-energize this equipment, turn off and unplug the UPS.
CAUTION! DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! Cyber-Power Systems does not sell products for life support
or medical applications. DO NOT use in any circumstance that would affect the operation or safety of any life support equipment, with any
medical applications, or patient care.
CAUTION! The battery can energize hazardous live parts inside even when the AC input power is disconnected.
CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity con-trolled indoor area, free of conductive
contaminants. (Please see specifications for acceptable tem-perature and humidity range).
CAUTION! To reduce the risk of electric shock, do not remove the cover, except to service the battery. There are no user serviceable parts
inside, except for the battery.
CAUTION! To avoid electrical shock, turn off the unit and unplug it from the AC power source before servicing the battery or installing a
computer component.
CAUTION! DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire, do not use with or near aquariums. Condensation
from the aquarium can come in contact with metal electrical contacts and cause the machine to short out.
CAUTION! DO NOT USE WITH LASER PRINTERS! The power demands of laser printers are too large for a UPS.
DESCRIPTION
1. LCD module display
LCD shows all the UPS information with icons and
messages.
2. Power On Indicator
This LED is illuminated when the utility condition is
normal and the UPS outlets are providing power,
free of surges and spikes.
3. Power Switch
Master on/off switch for equipment connected to the
battery power supplied outlets.
4. LCD function selected switch
The switch can be used to select the LCD display contents Including input/output voltage and estimated run time, etc.
5. Battery, Surge and AVR Outlets
Provides four battery power, surge protected and AVR outlets for connected equipment and ensures temporary uninterrupted operation of
your equipment during a power failure.
6. Surge Outlets
Provides two surge protected outlets for connected equipment.
7. Communication Protection Ports RJ11/RJ45
Communication protection ports will protect any standard modem, fax, telephone line, or network cable .
8. USB Port to PC
This port allows connection and communication from the USB port on the computer to the UPS unit. The UPS communicates its status to
the PowerPanel
®
Business Edition software. This interface is also compatible with the UPS application provided by Windows Vista and Mac
OS X.
9. Dry contact
This port produces information for equipment that can read dry contact signals.
10. Circuit Breaker
Located on the side of the UPS, the circuit breaker serves to provide overload and fault protection. Under normal operating conditions, the
circuit breaker is depressed.
11. Electrical Wiring Fault Indicator
This LED indicator will illuminate to warn the user that a wiring problem exists, such as bad ground, missed ground or reversed wiring. If
this is illuminated, disconnect all electrical equipment from the outlet and have an electrician check to ensure the outlet is properly wired.
12. AC Input
Connect the AC Power cord to a properly wired and grounded outlet.
13. Expansion Port
Allow users to add the optional SNMP card.
CAUTION! Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery.
Service the battery under the supervision of personnel knowledgeable of batteries and their
precautions.
CAUTION! Use only the specified type of battery. See your dealer for replacement batteries.
CAUTION! The battery may present the risk of electrical shock. Do not dispose of batteries in a fire,
as they may explode. Follow all local ordinances regarding proper disposal of batteries.
CAUTION! Do not open or mutilate the batteries. Released electrolyte is harmful to the skin and eyes
and may be toxic.
CAUTION! A battery can present a high risk of short circuit current and electrical shock. Take the
following precautions before replacing the battery:
1. Remove all watches, rings or other metal objects.
2. Only use tools with insulated handles.
3. DO NOT lay tools or other metal parts on top of battery or any battery terminals.
4. Wear rubber gloves and boots.
5. Determine if the battery is inadvertently grounded. If inadvertently grounded, remove
source of ground. CONTACT WITH A GROUNDED BATTERY CAN RESULT IN
ELECTRICAL SHOCK! The likelihood of such shock will be reduced if such grounds are removed during installation and maintenance
(applicable to a UPS and a remote battery supply not having a grounded circuit)
IMPORTANT SAFETY INSTRUCTIONS
(SAVE THESE INSTRUCTIONS)
INSTALLING YOUR UPS SYSTEM
BASIC OPERATION
Hardware Installation Guide
TROUBLE SHOOTING
BATTERY REPLACMENT
DEFINITIONS FOR ILLUMINATED LCD INDICATORS
Additional troubleshooting information can be found at www.cyberpowersystems.com/support.htm
Problem Possible Cause Solution
Full-time surge protection
outlets stop providing power
to equipment.
Circuit breaker has tripped
due to an overload.
Turn the UPS off and unplug at least one piece of equipment.
Wait 10 seconds, reset the circuit breaker by depressing the
button, and then turn the UPS on.
The UPS does not provide
expected runtime.
Recharge the battery by leaving the UPS plugged in.
Contact CyberPower Systems about replacement batteries at
tech@cyberpowersystems.com
Battery is slightly worn out.
Battery not fully charged.
The UPS will not turn on.
The on/off switch is designed
to prevent damage by rapidly
turning it off and on.
Turn the UPS off. Wait 10 seconds and then turn the UPS on.
The battery is worn out.
Contact CyberPower Systems about replacement batteries at
tech@cyberpowersystems.com
Mechanical problem.
Contact CyberPower Systems at
tech@cyberpowersystems.com
PowerPanel
®
Business
Edition is inactive.
The USB cable is not
connected.
Connect the USB cable to the UPS unit and an open
USB port on the back of the computer.
The unit is not providing
battery power.
Shutdown your computer and turn the UPS off. Wait 10
seconds and turn the UPS on. This should reset the unit.
BATTERY REPLACEMENT PROCEDURE:
1. Remove the right-side of the faceplate.
2. Remove the three retaining screws on
the cable protection cover then remove
the cover.
3. Disconnect the black and red cable.
4. Remove the retaining screw of the cable
connectors.
5. Replace the new battery pack. Assemble
the screws, cover, cable and front panel in
the reverse sequence of above steps.
Recharge the unit for 4-8 hours to ensure
the UPS performs expected runtime
4
1
5
2 3
1. Your new UPS may be used immediately upon receipt. However, recharging the battery for at least four hours is recommended to ensure
that the battery¡¦s maximum charge capacity is achieved. Charge loss may occur during shipping and storage. To recharge the battery,
simply leave the unit plugged into an AC outlet. The unit will charge in both the on and off position.
2. If you will use the software, connect the USB cable to the USB port on the UPS.
3. With the UPS unit off and unplugged, connect the computer, monitor, and any externally powered data storage device (Zip drive, Jazz
drive, Tape drive, etc¡K) into the battery power supplied outlets. DO NOT plug a laser printer, copier, space heater, vacuum, paper
shredder or other large electrical device into the UPS. The power demands of these devices will overload and possibly damage
the unit.
4. To protect a fax, telephone, modem line or network cable, connect a telephone cable or network cable from the wall jack outlet to the IN
jack of the UPS. Then connect a telephone cable or network cable from the OUT jack on the UPS to the modem, computer, telephone, fax
machine, or network device.
5. Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall outlet). Make sure the wall branch outlet is protected by a fuse or circuit
breaker and does not service equipment with large electrical demands (e.g. air conditioner, refrigerator, copier, etc¡K). Avoid using extension
cords. If used, the extension cord must be grounded and rated for 15 amps.
Line mode
Select SW
Press
UPS Status Display Capacity Display Digital Value Display
Initial
1st
2nd
3rd
4th
5th(Return)
Press >3sec
(Sound Disable)
Press >3sec
again
(Sound Enable)
(Overload)
Load
Cap.
V
V
V
X
V
V
--
--
--
Output
Voltage
V
V
--
--
--
Run
Time
V
--
--
--
% of
Load
V
--
--
--
% of
Batt.
V
--
--
--
Battery
Cap.
X
X
X
V
X
X
--
--
--
Input
Voltage
V
--
--
--
"V" : Illuminated, "X" : Not Illuminated, "--" : Either
X
X
X
X
X
X
X
X
X
V
V
V
V
V
V
V
V
V
--
--
--
--
--
--
V
X
--
RUN_TIMEOUTPUTINPUT
Min
V
%
LOAD BATT. CAP.
100
X
X
X
X
X
X
X
X
V
100
Battery mode
Select SW
Press
UPS Status Display Capacity Display Digital Value Display
Initial
1st
2nd
3rd
4th
5th(Return)
Press >3sec
(Sound Disable)
Press >3sec
again
(Sound Enable)
(Overload)
Load
Cap.
X
X
V
X
X
X
--
--
--
Output
Voltage
V
V
--
--
--
Run
Time
V
--
--
--
% of
Load
V
--
--
--
% of
Batt.
V
--
--
--
Battery
Cap.
V
V
X
V
V
V
--
--
--
Input
Voltage
V
--
--
--
"V" : Illuminated, "X" : Not Illuminated, "--" : Either
V
V
V
V
V
V
V
V
V
X
X
X
X
X
X
X
X
X
--
--
--
--
--
--
V
X
--
X
X
X
X
X
X
X
X
V
100
6. Depress the power switch to turn the unit on. The power on indicator light will illuminate and the unit will ¡§beep¡¨ once.
7. If an overload is detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn the UPS off and unplug at
least one piece of equipment from the battery power supplied outlets. Wait 10 seconds. Make sure the circuit breaker is depressed and
then turn the UPS on.
8. Your UPS is equipped with an auto-charge feature. When the UPS is plugged into an AC outlet, the battery will automatically recharge.
9. To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times.
10. To store your UPS for an extended period, cover it and store with the battery fully charged. Recharge the battery every three months to
ensure battery life.

Other manuals for CyberPower OR500LCDRM1U

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CyberPower OR500LCDRM1U and is the answer not in the manual?

CyberPower OR500LCDRM1U Specifications

General IconGeneral
Output power300 W
Input frequency60 Hz
Maximum current- A
Audible alarm(s)Yes
Surge energy rating1030 J
Output power capacity0.5 kVA
Weight (imperial)18 lbs
Dimensions (WxDxH)438.15 x 235 x 44.45 mm
Dimensions (W x D x H) (imperial)17.25 x 9.25 x 1.75 \
Battery technologySealed Lead Acid (VRLA)
Battery recharge time8 h
Typical backup time at full load3 min
Typical backup time at half load12 min
Form factor-
CertificationUL1778, cUL 107.1, FCC DOC Class B
Serial ports quantity1
USB 2.0 ports quantityUSB 2.0 ports have a data transmission speed of 480 Mbps, and are backwards compatible with USB 1.1 ports. You can connect all kinds of peripheral devices to them.
Operating temperature (T-T)0 - 40 °C
Operating relative humidity (H-H)0 - 95 %