19
1-8. Defrosting Mode
Input Control Object Contents Remark
1. Defrosting
Cycle
1. COMP
2. F-FAN
3. R-FAN
4. HEATER
C-FAN and
COMP are co-
working.
1. Defrosting Mode
2. Output Control Time & Limit Time of Each Defrosting Mode
PRE-COOL
Heater Defrosting
Pause Fan Delay
COMP ON OFF OFF ON
F-FAN ON OFF OFF OFF
R-FAN Control OFF OFF OFF
HEATER OFF ON OFF OFF
Limit
1
80 min.
Time
50 min.
2
40 min. 4 min. 5 min.
(if, D-Sensor Error)
1) Time = 50minutes
2) COMP & F-FAN : ON
R-fan : Control
Heater : OFF
3) If F-Sensor ≤ - 27°C, PRE-COOL function
turns OFF.
1) If D-Sensor ≥10 °C, Heater turns OFF.
2) Limit Time = 80minutes
3) If D-Sensor is in error, Heater turns ON for
the Limit Time of 40 minutes.
4) Limit Time
1
30 seconds : Heater is ON continuously
right after Defrosting Start regardless of
D-Sensor temperature.
2
40 minutes : if D1 Error
3
80 minutes : if in Normal Control
1) Time = 4 minutes
2) COMP, F-FAN, R-FAN : OFF
1) Time = 5 minutes
2) COMP : ON
F/R FAN : OFF
PRE-COOL
Pause
Fan Delay
Heater
Defrosting