Input Control Object Contents Remark
6. How to control in Error
1) F1 ERROR
1
Caused by F-Sensor Disconnection & Short
2
Control by letting COMP and F-Fan ON for 40 minutes, OFF for
20 minutes.
3
Terminated automatically if F-Sensor is normal.
2) r1 ERROR
1
Caused by R-Sensor Disconnection & Short
2
Control by ambient temperature
3
Terminated automatically if R-Sensor is normal
3) rt ERROR
1
Caused by RT Sensor Disconnection & Short
2
Control : Normal working (Deletion of control condition by RT-
Sensor)
3
Terminated automatically if RT Sensor is normal
4) d1 ERROR
1
Caused by D Sensor Disconnection & Short
2
Control : Limit Time of Defrosting Return 40 minutes
3
Terminated automatically if D Sensor is normal
5) door ERROR
1
Caused when door is sensed to be open for more than 1hour
2
Control : Deletion of Door Switch Sensing related functions
3
Terminated after display on C-LED
(Error Display Mode starts only when Door Switch is normal.)
6) C1 ERROR
1
Caused when COMP works continuously for more than 3 hours
under the condition of D-Sensor ≥ -5°C
2
Control : Normal Working
3
Terminated when D Sensor ≥ -5°C in COMP OFF
7) F3 ERROR
1
Caused when Defrosting returns by Limit Time of 80 minutes
2
Control by deleting Pre-Cool in Defrosting Mode
3
Terminated when Defrosting returns by D-Sensor
8) DF1 MODE : A/S Compulsive Defrosting Mode
1
Caused when pushing REF.SET Button 5 times while pushing
FRZ.SET Button
2
Control : A/S Compulsive Defrosting
3
Terminated when D-Sensor is over 10°C
RT-Sensor In Error ~13°C
14°C ~ 29°C
29°C ~
Working Rate
8 / 12 7 / 13 8 / 12 9 / 11
(ON/OFF)