CIrCUIT fUnCTIons
www.DaikinApplied.com 75 IOM 1206-7 • TRAILBLAZER
MODEL AGZ CHILLERS
Table 73: 6 Fans per Circuit - With 1 Fan VFD per Circuit
Circuit 1
Description Output Fans
Stage
1 2 3 4 5 6
Speed Signal 1 UC X5 Fan 11/13 On On On On On --
Fan Output 1 UC DO3 Fan 12 On On On --
Fan Output 2 UC DO4 Fan 14 On On --
Fan Output 3 UC DO5 Fan 15 On On On On --
Fan Output 4 UC DO6 Fan 16 On --
Condenser SV UC X7 SV 11 On On On On --
Circuit 2
Description Output Fans
Stage
1 2 3 4 5 6
Speed Signal 1 UC X6 Fan 21/23 On On On On On --
Fan Output 1 UC DO7 Fan 22 On On On --
Fan Output 2 UC DO8 Fan 24 On On --
Fan Output 3 UC DO9 Fan 25 On On On On --
Fan Output 4 UC DO10 Fan 26 On --
Condenser SV UC X8 SV 21 On On On On --
Table 74: 6 Fans per Circuit - With 2 Fan VFDs per Circuit
Circuit 1
Description Output Fans
Stage
1 2 3 4 5 6
Speed Signal 1 UC X5 Fan 11/13 On On -- -- --
Speed Signal 2 UC X2 Fan 12/14/15/16 On On -- -- --
Condenser SV UC X7 SV 11 On On
Circuit 2
Description Output Fans
Stage
1 2 3 4 5 6
Speed Signal 1 UC X6 Fan 21/23 On On -- -- --
Speed Signal 2 UC X3 Fan 22/24/25/26 On On -- -- --
Condenser SV UC X8 SV 21 On On --
Figure 59: 7 Fans per Circuit - Unit Numbering Schematic
Table 75: 7 Fans per Circuit - Without Fan VFD
Circuit 1
Description Output Fans
Stage
1 2 3 4 5 6
Fan Output 1 UC DO3 Fan 11/13
On
On On On On On
Fan Output 2 UC DO4 Fan 12 On On On
Fan Output 3 UC DO5 Fan 14/16 On On On
Fan Output 4 UC DO6 Fan 15 On On On On On
Fan Output 5 EEXV1 DO1 Fan 17 On
Condenser SV UC X7 SV 11 On
Circuit 2
Description Output Fans
Stage
1 2 3 4 5 6
Fan Output 1 UC DO7 Fan 21/23
On
On On On On On
Fan Output 2 UC DO8 Fan 22 On On On
Fan Output 3 UC DO9 Fan 24/26 On On On
Fan Output 4 UC DO10 Fan 25 On On On On On
Fan Output 5 EEXV2 DO1 Fan 27 On
Condenser SV UC X8 SV 21 On
Table 76: 7 Fans per Circuit - With 1 Fan VFD per Circuit
Circuit 1
Description Output Fans
Stage
1 2 3 4 5 6
Speed Signal 1 UC X5 Fan 11/13 On On On On On On
Fan Output 1 UC DO3 Fan 12 On On On On
Fan Output 2 UC DO4 Fan 14 On On On
Fan Output 3 UC DO5 Fan 15 On On On On On
Fan Output 4 UC DO6 Fan 16 On On
Fan Output 5 EEXV1 DO1 Fan 17 On
Condenser SV UC X7 SV 11 On
Circuit 2
Description Output Fans
Stage
1 2 3 4 5 6
Speed Signal 1 UC X6 Fan 21/23 On On On On On On
Fan Output 1 UC DO7 Fan 22 On On On On
Fan Output 2 UC DO8 Fan 24 On On On
Fan Output 3 UC DO9 Fan 25 On On On On On
Fan Output 4 UC DO10 Fan 26 On On
Fan Output 5 EEXV2 DO1 Fan 27 On
Condenser SV UC X8 SV 21 On
Table 77: 7 Fans per Circuit - With 2 Fan VFDs per Circuit
Circuit 1
Description Output Fans
Stage
1 2 3 4 5 6
Speed Signal 1 UC X5 Fan 11/13 On On On -- --
Speed Signal 2 UC X2
Fan
12/14/15/16
On On On -- --
Fan Output 5 EEXV1 DO1 Fan 17 On
Condenser SV UC X7 SV 11 On
Circuit 2
Description Output Fans
Stage
1 2 3 4 5 6
Speed Signal 1 UC X6 Fan 21/23 On On On -- --
Speed Signal 2 UC X3
Fan
22/24/25/26
On On On -- --
Fan Output 5 EEXV2 DO1 Fan 27 On
Condenser SV UC X8 SV 21 On --
Control Panel
Fan 11
Fan 12
Fan 21
Fan 23
Fan 15
Fan 13
Fan 24 Fan 22
Fan 14 Fan 16
Fan 25
Fan 26
Fan 27
Fan 17
7-Fan Unit Locations and Numbering