5 Electrical installation
Installation manual
12
EPRA14~18DAV3+W1
Daikin Altherma 3 H HT
4P586100-1 – 2019.07
Q1DI
1N~,
50 Hz,
230 V AC
F1B
1
3
2
4
II
BRN
BLU
YLW/GRN
b
a
L
N
a Factory-mounted power supply cable
b Field wiring
F1B Overcurrent fuse (field supply). Recommended fuse: 2
pole, 32A fuse, C curve.
Q1DI Earth leakage circuit breaker (30mA)(field supply)
2 Interconnection cable (indoor↔outdoor):
Route the cable through the frame.
Connect the wires to the terminal block (make sure the
numbers match with the numbers on the indoor unit) and the
earth screw.
Fix the cable with a cable tie.
Wires: (3+GND)×1.5mm²
1 2 3
1
2
3
3 (Optional) Drain tube heater cable:
Make sure the heating element of the drain tube heater is
completely inside the drain tube.
Route the cable through the frame.
Connect the wires to the terminal block and the earth screw.
Fix the cable with cable ties.
Wires: (2+GND)×0.75mm². Wiring must be double insulated.
Maximum power allowed for drain tube heater = 115W (0.5A)
L N PE
1 2
4 (Optional) Power saving function: If you want to use the
power saving function:
Disconnect X804A from X805A.
Connect X804A to X806A.
X806A
X804A
X805A
INFORMATION
Power saving function. The power saving function is only
applicable for V3 models. For more information about the
power saving function ([9.F] or overview field setting
[E‑08]), see the installer reference guide.
5.3.2 In case of W1 models
1 Power supply cable: