3 Unit installation
Installation manual
7
EPRA14~18DAV3+W1
Daikin Altherma 3 H HT
4P586100-1 – 2019.07
2 Fix the unit to the installation structure.
M12
3 Remove the slings (and screws), and dispose of them.
3.2.3 To provide drainage
Make sure that condensation water can be evacuated properly.
NOTICE
If the unit is installed in a cold climate, take adequate
measures so that the evacuated condensate CANNOT
freeze. We recommend to do the following:
Insulate the drain hose.
Install a drain tube heater (field supply). To connect the
drain tube heater, see "5.3 To connect the electrical
wiring on the outdoor unit"on page11.
NOTICE
Provide at least 150 mm of free space below the unit.
Additionally, make sure the unit is positioned at least
100mm above the expected level of snow.
Use the drain plug (with O-ring) and a hose for drainage.
1 2
a
b
c
c
3
d
a Drain hole
b O-ring (delivered as accessory)
c Drain plug (delivered as accessory)
d Hose (field supply)
NOTICE
O-ring. Make sure the O-ring is installed correctly to
prevent leakage.
3.3 To open the outdoor unit
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING

Other manuals for Daikin Altherma 3 H HT